Setting the functions of the ACP BACnet
The following functions can be set by using the menu of the ACP BACnet:
Select Peak or Demand
Setting the attributes of CH6
Fire Alarm function
Fahrenheit/Celsius setting function
Device ID setting function
Vnet number setting function
Foreign Device register function
Before setting the functions of the ACP BACnet
The function setting of the ACP BACnet should be changed depending on the case that only the ACP
BACnet is used or the case that the ACP BACnet is interconnected with the external devices such as
AC Manager, power distribution indicator, and Demand controller.
In general, the function of the ACP BACnet should be set and used as follows:
Peak or demand selection
function
Schedule function
Power display function
Caution
Setting to use the power display
If the ACP BACnet and the power distribution indicator are not connected, the power display
function should be set to no-use.
If it is set to use, be careful since the control speed of the ACP BACnet will be slower.
When only ACP BACnet is
used
Set to peak function
Set to use schedule function
Set to use if it interfaces with power distribution indicator, and set
to no-use if it does not interface..
Installing ACP BACnet
When ACP BACnet interfaces
with AC Manager
Set to demand function
Set to no-use of schedule
function