Honeywell VISTA-128BPT Programming Manual page 91

Burglary partitioned security system
Hide thumbs Also See for VISTA-128BPT:
Table of Contents

Advertisement

A =
DEVICE ACTION
EV =
EVENT
ZL =
ZONE LIST
ZT =
ZONE TYPE/SYSTEM OPERATION
Choices for Zone Types are:
00=zone not used
01=entry/exit 1
02=entry/exit 2
03=perimeter
04=interior (follower)
05=day/night burglary
06=24 hour silent
07=24-hour audible
NOTE:
Choices for System Operation are:
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
16 = Fire With Verification
20 = Arming-STAY***
21 = Arming-AWAY****
22 = Disarming (Code + Off)
23 = No Alarm Response
*
Stop condition only
**
Or at Disarming, whichever occurs earlier
*** The output also activates when the partition is armed in the INSTANT mode
**** The output also activates when the partition is armed in the MAXIMUM mode
P =
PARTITION No. 1-8, 0 = Any
ZONE LISTS FOR OUTPUT DEVICES – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in
the required data on the worksheet below and follow the procedure shown earlier in this Programming Guide as you enter
the data during the displays and prompts that appear in sequence. Up to 15 zone lists may be created
NOTE:
Record desired zone numbers below. More or fewer boxes than shown may be needed, as any list may include
any or all of system's zone numbers.
Zone List 1: Started or stopped by zone numbers (enter 000 to end entries).
Zone List 2: Started or stopped by zone numbers (enter 000 to end entries).
0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 =
Toggle alternately between START and STOP events
0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble
01-15, 00 = Not Used
"START" ZONE LIST:
"STOP" ZONE LIST:
08=24-hour auxiliary
09=supervised fire
10=interior (delay)
12=Not Used
14=CO detector alarm
16=fire w/verification
20=arm stay
21=arm away
Any zone in "ZT" for Start, going into alarm, fault, or trouble will activate the relay.
Any zone in "ZT" for Stop, that restores will stop the relay action.
27 = Access Point (allows more than
one relay to be controlled by
activation if access point
request)
28 = MLB Supervision
29 = Momentary Exit
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout **
38 = Chime
39 = Fire Alarm
40 = Bypassing
41 = AC Power Fail
SECTION 4: SYSTEM LAYOUT WORKSHEETS
Upon alarm, fault, trouble or restore of ANY zone in this list, device
action will START.
Upon restore of ALL zones on this list, device action will STOP. It
need not be same list as used for START.
22=disarm
23=no alarm response
26=Not Used
27=Not Used
28=Not Used
29=momentary exit
87
42 = System Battery Low
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
47 = Console Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field
1∗74) *
57 = YY Seconds (enter YY in field
1∗75) *
58 = Duress
60 = Audio Alarm Verification (must be
selected for both START and
STOP operation)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250bptVista-128bptsia

Table of Contents