FIELD
TITLE and DATA ENTRIES
RF Receiver Supervision Check-in Interval
1∗30
Enter 02-15 times 2 hours (4-30 hours).
00 = disable receiver supervision.
Select the check-in monitoring interval for the RF receiver(s).
Failure of a receiver to receive any RF signal within the time entered results in the activation of the response type
programmed for zone 990 for the first receiver and zone 988 for the second receiver and their related communication
reports.
UL
MAXIMUM IS 2 (4 HR) FOR UL INSTALLATIONS.
RF Transmitter Check-in Interval
1∗31
Enter 02-15 times 2 hours (4-30 hours).
00 = disable transmitter supervision.
Select the check-in monitoring interval for the RF transmitters.
A failed supervision message sends if no check-in is received during the established time period. (Each transmitter sends
a check-in messages every 70-90 minutes.)
UL
MAXIMUM IS 2 (4 HR) FOR UL INSTALLATIONS.
1∗34
Communicator Split Reporting
0 = Split Reporting disabled
1 = Alarm, Alarm Restore, and Cancel reports to primary, all
others to secondary.
2 = Open/Close and Test reports to secondary, all other reports
to primary.
Select the type of split reporting for system communication.
NOTE: See ∗51 for split/dual reporting combinations.
Split reporting should not be used with Dynamic Signaling, as reports split to Secondary are not sent to the ECP
Communicator.
Access Control Dialer Enables
1∗35
0 = disable
1 = enable
If Trace is enabled, access grant/denial events send to the central station.
If enabled, the other events send a report to the central station.
Call Waiting Defeat
1∗42
0 = disable
1 = enable
If enabled, the system defeats Call Waiting, dialing ∗70 on the first outgoing call attempt to both the primary and
secondary numbers.
DO NOT enable this feature unless Call Waiting is being used.
Permanent Keypad Display Backlighting (partition-
1∗43
specific)
0 = disable
1 = enable
Enabled:
Backlighting for the keypad display remains on at all times.
Disabled:
The backlighting comes on when a key is pressed. When a key is pressed, display backlighting turns on
for all keypads in that partition.
NOTE: This field affects only standard keypads, not graphic/touch-screen keypads.
Wireless Keypad Tamper Detect
1∗44
0 = disable
1 = enable
If enabled, when more than 40 key depressions are received without a valid sequence (arm, disarm, etc.), the control panel
disables the wireless keypad.
This inhibit is removed once a valid key sequence is received from a wired keypad.
UL
WIRELESS KEYPAD IS NOT SUITABLE FOR USE IN A UL INSTALLATION.
SECTION 3: DATA FIELD DESCRIPTIONS
Default Values
[06]
E
E
A
A A
[12]
E
E
A
A A
[0]
E
A
[000000]
A
T race
E
[0]
E
A
[0]
E
A
[0]
E
A
29
A
A
A
A
A
A
A
A
A
A
T rbl
B yp
N /U
S yst
A lm
E
E
E
E
E
E
E
E
E
E
E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250bptVista-128bptsia

Table of Contents