Honeywell VISTA-128BPT Programming Manual page 39

Burglary partitioned security system
Hide thumbs Also See for VISTA-128BPT:
Table of Contents

Advertisement

FIELD
TITLE and DATA ENTRIES
Enable GOTO for this Partition (partition-specific)
2∗18
0 = disable
1 = enable
Enabled: Selected partition can be accessed from another partition's keypad using the GOTO command.
• User must be programmed as a multi-access user.
• Press their code + ∗ + partition # to switch partitions.
• Press their code + ∗ + 0 to switch back to the keypads home partition.
• Time out after two minutes of no keypad activity.
Use Partition Descriptor
2∗19
0 = disable
1 = enable
Enabled: Normal keypad display will include a partition number and four-digit descriptor.
Display Fire Alarms of Other Partitions (partition-
2∗22
specific)
0 = disable
1 = enable
If enabled, allows fire alarms that occur on other partitions to be displayed at this partition's keypad(s).
Display Burg, Panic and CO Alarms for Other Partitions
2∗23
(partition-specific)
0 = disable
1 = enable
If enabled, allows burglary, panic and CO alarms that occur on other partitions to be displayed at this partition's keypad(s).
Display Troubles of Other Partitions (partition-specific)
2∗24
0 = disable
1 = enable
If enabled, allows troubles that occur on other partitions to be displayed at this partition's keypad(s).
SECTION 3: DATA FIELD DESCRIPTIONS
Default Values
[1]
E
A
[0]
E
A
[0]
E
A
[0]
E
A
[0]
E
A
35

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vista-250bptVista-128bptsia

Table of Contents