PROMPT
02 START: ACS PT
(00-15)
00
02 START: PARTN
ANY PARTITION
0
Do not use a zone programmed with an RF Button (Input Type BR) to STOP a relay. The system will not
de-activate the relay.
02 STOP: ZN LIST
00
02 STOP: ZN TYPE
NO RESPONSE
00
02 STOP: ACS PT
(00-15)
00
02 STOP: PARTN
ANY PARTITION
0
02 RELAY GROUP
00
02 RESTRICTION
1=YES 0=NO
0
02 RELAY TYPE
V-PLEX
0
02 V-PLEX ZONE #
000
02 ECP ADDRESS
00
02 MODULE RELAY#
0
When all relays have been programmed, enter 00 at the "ENTER RELAY NO." prompt.
If you are defining a zone list, continue to the next section. If not, enter 00 + [∗] at the next two prompts. "Quit Menu
Mode?" appears enter 1 for "Yes," 0 for "No." Then enter ∗99 to exit programming completely.
EXPLANATION
If the start zone type you selected was 27 (access point), this prompt is displayed. Enter the access point
(00-15) that will start the relay action. Applies to WIN-PAK® or Pro-Watch®
Press [∗] to continue.
If the starting event will be limited to occurring on a specific partition, enter the partition number (1-8) in
which the start event will occur. Enter 0 for any partition.
Press [∗] to continue.
If a zone list is being used to stop this relay action, enter the zone list number, 1-15. The restore of a
zone on the zone list stops the relay. If a zone list is not being used, enter 0.
Press [∗] to continue.
If a Zone Type/System Operation is being used to stop the relay action, enter the 2-digit code listed in
the Choices for Start/Stop System Operation chart. The restore of the Zone Type or System Operation
stops the relay.
Press [∗] to continue.
If the stop zone type you selected was 27 (access point), this prompt is displayed. Enter the access point
(00-15) which will stop the relay action.
Press [∗] to continue.
This is the partition to which the stop condition will be limited. Enter 0 for any partition. Enter 1-8 for
specific partition number.
Press [∗] to continue.
Relays may be grouped for common activation by time-driven events (commands 06-10), time-driven
events are found in the "Scheduling" section in the Installation and Setup Guide. Enter 00 (no group) or
01-15 for a specific group number.
Press [∗] to continue.
The system may have some devices that are not intended to be under end user control, such as relays
activating fire doors or machinery. Enter 1 if the end user will be restricted from accessing this relay
using their Code #70 manual relay control.
Press [∗] to continue.
Enter 0 for V-Plex 4101-SN (polling loop) devices. Enter 1 for (ECP) relay module 4204.
Press [∗] to continue.
For polling loop trigger outputs (4101SN), enter the protection zone number (010 - 250) linked to each
output. Be sure to enroll the module's serial number (see Zone Programming).
Press [∗] to continue.
If you selected 1 for (4204), enter the actual module's address (01-30).
Press [∗] to continue.
For 4204 Relay Outputs, enter the specific relay number on that module (1-4).
Press [∗] to continue.
The keypad will display the Start and Stop summary screens again.
Press [∗] to continue.
SECTION 3: DATA FIELD DESCRIPTIONS
65