VLT
AQUA Drive
Operating Instructions
22-35 Low Speed Power [HP]
Range:
0 hp*
[0.00 - 0.00 hp]
22-36 High Speed [RPM]
Range:
0 RPM*
[0 - par. 4-13 RPM]
22-37 High Speed [Hz]
Range:
0.0 Hz*
[0.0 - par. 4-14 Hz]
22-38 High Speed Power [kW]
Range:
0 kW*
[0.00 - 0.00 kW]
22-39 High Speed Power [HP]
Range:
0 hp*
[0.00 - 0.00 hp]
22-40 Minimum Run Time
Range:
10 s*
[0 - 600 s]
22-41 Minimum Sleep Time
Range:
10 s*
[0 - 600 s]
22-42 Wake-up Speed [RPM]
Range:
0 RPM*
[par. 4-11 - par. 4-13 RPM]
Function:
Settings
To be used if par. 0-03 Regional
International selected).
Set power consumption at 50% speed level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Speed Unit
To be used if par. 0-02 Motor
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
Function:
Speed Unit
To be used if par. 0-02 Motor
Set used speed for the 85% level.
The function is used for storing values needed to tune No Flow Detection.
Function:
Settings
To be used if par. 0-03 Regional
North America selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Settings
To be used if par. 0-03 Regional
International selected).
Set power consumption at 85% speed level.
This function is used for storing values needed to tune No Flow Detection.
Function:
Set the desired minimum running time for the motor after a Start command (digital input or Bus)
before entering Sleep Mode.
Function:
Set the desired minimum time for staying in Sleep Mode. This will override any wake up conditions.
Function:
To be used if par. 0-02 Motor
Speed Unit
Only to be used if par. 1-00
Configuration Mode
by an external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
®
MG.20.M5.02 - VLT
is a registered Danfoss trademark
8. How to programme the frequency converter
has been set for North America (parameter not visible if
has been set for RPM (parameter not visible if Hz selected).
has been set for Hz (parameter not visible if RPM selected).
has been set for International (parameter not visible if
has been set for North America (parameter not visible if
has been set for RPM (parameter not visible if Hz selected).
is set for Open Loop and speed reference is applied
8
99