22-84 Speed at No-Flow [Hz]
Range:
50.0 Hz*
[0.0 - par. 22-86 Hz]
22-85 Speed at Design Point [RPM]
Range:
1500. RPM* [par. 22-83 - 60000. RPM]
22-86 Speed at Design Point [Hz]
Range:
50/60.0
[par. 22-84 - par. 4-19 Hz]
Hz*
22-87 Pressure at No-Flow Speed
Range:
0.000 N/A*
[0.000 - par. 22-88 N/A]
22-88 Pressure at Rated Speed
Range:
999999.999
[par. 22-87 - 999999.999 N/A]
N/A*
22-83 Speed at No-Flow [RPM]
Range:
300. RPM*
[0 - par. 22-85 RPM]
22-90 Flow at Rated Speed
Range:
0.000 N/A*
[0.000 - 999999.999 N/A]
Function:
Resolution 0.033 Hz.
The speed of the motor at which flow has effectively stopped and minimum pressure H
should be entered here in Hz. Alternatively, the speed in RPM can be entered in par. 22-83
at No-Flow [RPM]
. If it has been decided to use Hz in par. 0-02 Motor
22-86
Speed at Design Point [Hz]
until minimum pressure H
is achieved will determine this value.
MIN
Function:
Resolution 1 RPM.
Only visible when par. 22-82
Work Point Calculation
which the System Design Working Point is achieved should be entered here in RPM. Alternatively,
the speed in Hz can be entered in par. 22-86
Speed Unit
use RPM in par. 0-02 Motor
used.
Function:
Resolution 0.033 Hz.
Work Point Calculation
Only visible when par. 22-82
which the System Design Working Point is achieved should be entered here in Hz. Alternatively, the
speed in RPM can be entered in par. 22-85
Speed Unit
use Hz in par. 0-02 Motor
Function:
Enter the pressure H
corresponding to Speed at No Flow in Reference/Feedback Units.
MIN
Function:
Enter the value corresponding to the Pressure at Rated Speed, in Reference/Feedback Units. This
value can be defined using the pump datasheet.
Function:
Resolution 1 RPM.
The speed of the motor at which flow Is zero and minimum pressure H
entered here in RPM. Alternatively, the speed in Hz can be entered in par. 22-84
[Hz]
. If it has been decided to use RPM in par. 0-02 Motor
Design Point [RPM]
should also be used. Closing the valves and reducing the speed until minimum
pressure H
is achieved will determine this value.
MIN
Function:
Enter the value corresponding to Flow at Rated Speed. This value can be defined using the pump
datasheet.
®
MG.20.M5.02 - VLT
is a registered Danfoss trademark
8. How to programme the frequency converter
should also be used. Closing the valves and reducing the speed
is set to
Disable
. The speed of the motor at
Speed at Design Point [Hz]
Speed at No-Flow [RPM]
then par. 22-83
Disable
is set to
. The speed of the motor at
Speed at Design Point [RPM]
Speed at No-Flow [RPM]
, then par. 22-83
Speed Unit
is achieved
MIN
Speed
Speed Unit
then par.
. If it has been decided to
should also be
8
. If it has been decided to
should also be used.
is achieved should be
MIN
Speed at No-Flow
Speed at
then par. 22-85
103