Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder
suppression options.

Relay Programming

The VISTA-100 supports up to 16 relay outputs. Relays can be used to perform many
different functions and actions. You must program each relay to begin one of four types of
ACTIONS at a designated START event, and end that ACTION at a designated STOP
event. The options used to start and stop these devices are described below, followed by the
actual screen prompts and available entries.
The letter(s) in parentheses after each function described below, such as (A) after ACTION,
are those that appear in the various summary displays of programmed data during
programming.
ACTION (A)
22-6
If you entered device type 1 (alpha keypad), this prompt will
appear. You can program keypads individually to suppress
arm/disarm beeps, entry/exit beeps, and Chime mode beeps.
This helps prevent unwanted sounds from disturbing users.
Enter a number 00-03 for the keypad-sounding suppression
options you want for the keypad as follows:
00 = no suppression
01 = suppress arm/disarm & entry/exit beeps
02 = suppress Chime mode beeps only
03 = suppress arm/disarm, entry/exit, and Chime mode
beeps
If you entered device type 1 (alpha keypad), this prompt will
appear. You can set up each keypad so that users with access
to multiple partitions can arm and disarm them through the
keypad. To enable this keypad for global arming and
disarming, enter 1. To prevent global arming and disarming
from this keypad, enter 0.
The screen will display the next device number to be
programmed.
Press 00 +
Press *99 to exit Program Mode.
Enter [Installer Code] + OFF to cancel the system's settling
delay.
The ACTION of the device is how the device will respond when it is
activated by the START programming. You might want the device to
activate momentarily, to pulse on and off continuously, or to remain
activated until some other event occurs to stop it. There are four
different actions:
• ACTIVATE for 2 SECONDS and then reset
• ACTIVATE and REMAIN ACTIVATED until stopped by some other
event
• PULSE ON and OFF until stopped by some other event
• NO RESPONSE when the device is not used
to exit Menu Mode.