External Sounder Connections - ADEMCO VISTA-100 Isntallation Instructions And Programming Manual

Commercial fire and burglary partitioned security system with scheduling
Hide thumbs Also See for VISTA-100:
Table of Contents

Advertisement

Model
System Sensor MASS121575 ADA
System Sensor MA/SS-12
Wheelock LS1-12-VFR
Wheelock MS1-12-VFR
Wheelock MT-12-LS-VFR
Wheelock MT4-12-LS-VFR
Wheelock MT-12-MS-VFR
Wheelock MT4-12-MS-VFR
Gentex GXS-2-15
Gentex GXS-2-1575
Gentex SHG-12-15
Gentex SHG-12-1575
Faraday 5336L-U-14-12-DC
Faraday 5337L-U-14-12-DC
(Shows wiring for bell outputs configured using factory default programming selections)
BELL 1 FACTORY DEFAULTS
Bell 1 is configured as a burglary bell circuit
• Use nonpolarized Grade A indicating devices
(e.g., ADEMCO No. AB12 - see wiring notes
below)
• Wiring is not supervised; cut white jumper, W1,
on main PCB
• Activates for Zones 3-8 alarms (by default,
Zones 3-8 are assigned to burglary partition 1)
• Steady alarm output
• 16-minute timeout
BELL 2 FACTORY DEFAULTS
Bell 2 is configured as a fire bell circuit
• Use polarized indicating
devices
• Class B open/short supervision
• 24-hr. trouble response to faults
• Activates for Zone 1-2 alarms (by default,
Zones 1-2 are assigned to fire partition 3)
• Pulsed alarm output
• No timeout
AB12 BELL/BOX WIRING
1
2
3
BELL
Figure 13-1. External Sounder Connections
Description
Horn/Strobe
Horn/Strobe
Strobe
Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Strobe
Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
3
4
+
-
BELL 1
AB12 WIRING NOTES:
• Disconnect the AB12's factory-wired connection
from its terminal #4 to its outer box.
• Set field 3
function.
• Assign Zone 6 to a burglary partition. Program
it for day trouble/night alarm response (type 05)
when this bell is used by only one burglary
partition. Program it for 24-hr. audible alarm
response (type 07) when this bell is used by
more than one burglary partition.
• All wiring from AB12 to panel must be run in
conduit.
2k EOLR
4
5
6
AB12 OUTER BOX
TAMPER
SWITCHES
INNER LINER
Section 13 - External Sounders
5
6
-
+
BELL 2
2k EOLR
(Model 610-7)
17 to "1" to enable Zone 6 tamper
*