Insulation Test Voltage

Insulation Test Voltage
Type test, insulation test voltage
500 V a.c. or 700 V d.c. 1 minute for RIV 50V
2000 V a.c. 1 minute for RIV 250V modules
Routine Test, insulation test voltage
850 V d.c. 1 second for RIV 50V modules
2000 V a.c. 1 second for RIV 250V modules
1. Modules with a working voltage of less than 50 V have RIV 50 V. RIV 250 V applies to all modules having a
working voltage greater than 50 V. It should be noted that insulation test voltage specifications, according to
electrical safety standards, do not imply that permanent connection to circuits with voltages greater than the
specified Rated Insulation Voltage is allowed. Connection to voltages higher than specified RIV violates
electrical safety codes and may expose users to electric shock.
120
Section 3 Technical Data and Performance
1
modules