Section 2 Product Description
Mounting
The I/O station can be mounted horizontally, vertically or in combinations
(Figure 53
used depending on available space and preferred way of installing the field wiring
(external marshalling/power distribution or direct on Extended MTUs using built in
2/3 wire termination and power distribution arrangements). Compact and Extended
MTUs as well as S800L modules can be mixed and matched within the I/O station
to suit the required field termination.
The S800 I/O is mounted on a DIN-rail. The DIN-rail is mounted in a cabinet or on
an enclosure wall to a metal sheet with fastening screws every 100 mm to ensure a
good chassis ground connection in the cabinet or on an open track. The FCI,
ModuleBus Modem, MTUs and S800L I/O modules are mounted on the DIN-rail.
It is recommended to use end supports when mounting the I/O station.
In environments with major vibrations, the MTUs shall be screwed on the metal
sheet.
Figure 53. Horizontal Mounting of 1 FCI (left) and 12 S800M I/O MTUs (Compact)
84mm
120mm
(4.72")
(3.3")
Figure 54. Horizontal Mounting of 1 FCI (left) and 12 S800M I/O MTUs (Extended)