Section 3 Technical Data and Performance
Table 41. DO890 Digital Input Module Intrinsic Safety Parameters
Safety
Terminals
description
Powered
U
= 26 V
0
output
I
= 93 mA
0
terminals
P
= 605 mW IIA
0
3BSE015969-600 A
Maximum external parameters
Groups CENELEC USA
IIC
AB
IIB
CE
DFG
Intrinsic Safety Parameters
C
(uF)
L
(mH)
0
0
0.099
4.1
0.77
16.4
2.6
32.8
L/R (uH/O)
58
234
469
163