G3 Compliant; Transport And Storage Conditions - ABB S800 Product Manual

Table of Contents

Advertisement

Section 3 Technical Data and Performance

G3 Compliant

The G3 compliant modules fulfills the severity level in the standard ISA-S71.04
Environmental Conditions for Process Measurement and Control Systems: Airborne
Contaminants.
The G3 compliant modules shall not be stored in more severe environment than G2
if the contacts are unconnected.

Transport and Storage Conditions

The S800 modules should be transported and stored in their original packaging.
Temperature
Humidity
Altitude
Pollution degree
Corrosive
atmosphere
Fall in package
Shock
3BSE015969-600 A
Table 13. S800 Storage Conditions
Condition
-40 to +70°C
RH = 5 to 95%, no condensation
-500 to +3000 m
Degree 2
< 1000 Angstrom copper corrosion over
28 days
< 10 kg: 300 mm
10 - 40 kg: 300 mm
> 40 kg: 250 mm
Free-fall drop height in original product
package.
150 m/s
Range
2
, 11 ms
G3 Compliant
Standard
IEC/EN 61131-2
IEC 60664-1
ISA-71.04 
Severity level G2
IEC/EN 61131-2
115

Hide quick links: