ABB S800 Product Manual page 48

Table of Contents

Advertisement

I/O Modules
Analog I/O Modules
All the analog I/O modules have galvanic isolation relative to chassis ground in a
group of 4 or 8 channels. Some of the modules also has isolation between channels.
The modules have the standard set of module status indicators.
The open circuit detection is available for inputs and outputs configured for 4...20
mA and for the RTD and TC inputs.
Module
Type
AI801
AI810
AI815
AI820
AI825
48
Table 7. S800 Analog Modules
L Analog Input 1*8 channels. 0...20 mA, 4...20 mA, 
12 bit., 0.1% 
Current shunt resistor 250 is protected to 30 V. 
Rated insulation voltage 50 V.
Analog Input 1*8 channels. 0...20 mA, 4...20 mA,
0...10 V, 2...10 V, 12 bit., 0.1% 
Current shunt resistor 250 is protected to 30 V. 
Rated insulation voltage 50 V.
Analog Input 1*8 channels. 0...20 mA, 4...20 mA,
0...5 V, 1...5 V, 12 bit., 0.1% 
Current shunt resistor 250 is protected to 11 V. 
Rated insulation voltage 50 V.
Analog Input differential 1*4 channels. -20...20 mA,
0...20 mA, 4...20 mA, -5...5 V, 0...5 V, 1...5 V, -10...10 V,
0...10 V, 2...10 V, 14 bit + sign, 0.1%, CMV 50 V.
Current shunt resistor 250 is protected to 30 V. 
Rated insulation voltage 50 V
Analog Input 4*1 channels for applications requiring
galvanic isolated channels, -20...20 mA, 0(4)...20 mA, -
10...10V, 0(2)...10 V
Section 2 Product Description