PROFIBUS CI801
Calculation of Number of S800 I/O Modules per Station
Due to the PROFIBUS-DP specification it is not possible to always connect 24
I/O modules to one FCI. This is because the S800 I/O system includes more data
and user parameters than PROFIBUS-DP can handle.
number of modules that can be connected to one CI801.
126
Table 24. Maximum Number of Modules on CI801
Module Type
AI801, AI810, AI830, AI830A, AI835,
AI835A, AI890, AI893, AI895
AI820, AI825
AI843
AI815, AI845
AO801, AO810, AO810V2, AO890,
AO895
AO820
AO815, AO845, AO845A
DI801, DI802, DI803, DI810, DI811,
DI820, DI821
DI818
DI828
DI840
DO801, DO810, DO814
DO818
DO802, DO815, DO820, DO821
DO828
DO840
DP820
Section 3 Technical Data and Performance
Table 24
Number of Modules
14 (11)
24 (22)
11 (9)
14 (11)
7 (5)
14 (11)
7 (5)
24 (24)
24 (24)
24 (24)
16 (16)
22 (21)
13 (13)
24 (24)
22 (21)
20 (19)
8 (6)
shows maximum
3BSE015969-600 A