Intrinsic Safety Parameters - ABB S800 Product Manual

Table of Contents

Advertisement

Section 3 Technical Data and Performance

Intrinsic Safety Parameters

The following Intrinsic Safety parameters apply for AI890
Table
Table
Table 36. AI890 Analog Input Module Intrinsic Safety Parameters
Safety
Terminals
Description
Powered
U
= 27 V
0
transmitter
I
= 92 mA
0
terminals
P
= 621 mW
0
Passive
U
= 30 V
0
input
I
= 1.25 mA
(1)
0
terminals
P
= 937 mW
0
(1) Non energy-storing apparatus connection
Table 37. AI893 Analog Input Module Intrinsic Safety Parameters
Safety
Terminals
description
Input
U
= 12 V
0
terminals
I
= 20 mA
0
P
= 60 mW
0
3BSE015969-600 A
37, AI895
Table
38, AO890 and AO895
41.
Groups CENELEC USA
IIC
IIB
IIA
IIC
IIB
IIA
Groups CENELEC USA
IIC
IIB
IIA
Table
Maximum External Parameters
C
(uF)
0
AB
0.089
CE
0.74
DFG
2.23
AB
-
CE
-
DFG
-
Maximum external parameters
C
(uF)
0
AB
1.41
CE
9
DFG
36
Intrinsic Safety Parameters
Table
36, AI893
39, DI890
Table 40
and DO890
L
(mH)
L/R (uH/O)
0
4.1
16.4
32.8
-
-
-
L
(mH)
L/R (uH/O)
0
88
352
706
55
221
445
-
-
-
586
2347
4707
161