2 PRODUCT DESCRIPTION
2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times include the activation time of a trip rated form-A output contact unless otherwise indicated.
FlexLogic operands of a given element are 4 ms faster. Take this into account when using FlexLogic to interconnect
with other protection or control elements of the relay, building FlexLogic equations, or interfacing with other IEDs or
NOTE
power system devices via communications or different output contacts. If not specified, operate times are given
here for a 60 Hz system at nominal system frequency. Operate times for a 50 Hz system are 1.2 times longer.
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
0.1 to 2.0 × CT:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 × CT:
±1.5% of reading > 2.0 × CT rating
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type:
Instantaneous/Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
Voltage restraint:
Modifies pickup current for voltage in the
range of 0.1<V<0.9 VT Nominal in a
fixed linear relationship
PHASE/NEUTRAL/GROUND IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0 × CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0 × CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
Operate time:
<16 ms at 3 × pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3 × pickup at 60 Hz
(Neutral IOC)
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
GE Multilin
NEGATIVE SEQUENCE TOC
Pickup level:
Dropout level:
Level accuracy:
Curve shapes:
Curve multiplier (Time dial): 0.00 to 600.00 in steps of 0.01
2
t; FlexCurves™
Reset type:
Curve timing accuracy
at 1.03 to 20 x pickup:
NEGATIVE SEQUENCE IOC
Pickup level:
Dropout level:
Level accuracy:
Overreach:
Pickup delay:
Reset delay:
Operate time:
Timer accuracy:
WATTMETRIC ZERO-SEQUENCE DIRECTIONAL
Measured power:
Number of elements:
Characteristic angle:
Minimum power:
Pickup level accuracy:
Hysteresis:
Pickup delay:
Inverse time multiplier:
Curve timing accuracy:
Operate time:
F35 Multiple Feeder Protection System

2.2 SPECIFICATIONS

2.2.1 PROTECTION ELEMENTS

0.000 to 30.000 pu in steps of 0.001
97% to 98% of pickup
±0.5% of reading or ±0.4% of rated
(whichever is greater)
from 0.1 to 2.0 x CT rating
±1.5% of reading > 2.0 x CT rating
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
2
Extremely Inverse; I
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Instantaneous/Timed (per IEEE) and Lin-
ear
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
0.000 to 30.000 pu in steps of 0.001
97 to 98% of pickup
0.1 to 2.0 × CT rating: ±0.5% of reading
or ±0.4% of rated (whichever is greater);
> 2.0 × CT rating: ±1.5% of reading
<2%
0.00 to 600.00 s in steps of 0.01
0.00 to 600.00 s in steps of 0.01
<20 ms at 3 × pickup at 60 Hz
±3% of operate time or ±1/4 cycle
(whichever is greater)
zero-sequence
4
0 to 360° in steps of 1
0.001 to 1.200 pu in steps of 0.001
±1% or ±0.0025 pu, whichever is greater
3% or 0.001 pu, whichever is greater
definite time (0 to 600.00 s in steps of
0.01), inverse time, or FlexCurve
0.01 to 2.00 s in steps of 0.01
±3.5% of operate time or ±1 cycle
(whichever is greater) from pickup to
operate
<30 ms at 60 Hz
2
2-9