5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 PID 1
 REGULATOR
5
5-186


PID REGULATOR

PID 1
FUNCTION: Disabled
PID 1 SAMPLE TIME:
MESSAGE
0.05 s
PID 1 PROCESS
MESSAGE
SIGNAL: Off
PID 1 SETPOINT
MESSAGE
SIGNAL:
PID 1 TRACKING SIGNAL:
MESSAGE
Off
PID 1 PROPORTIONAL
MESSAGE
GAIN: 1.00
PID 1 SETPOINT
MESSAGE
WEIGHTING: 1.00
PID 1 INTEG. TIME
MESSAGE
CONST.: 1.00 sec
PID 1 ANTIWINDUP:
MESSAGE
Disabled
PID 1 AW TIME CONST.:
MESSAGE
1.00 sec
PID 1 DERIV. TIME
MESSAGE
CONST.: 1.00 s
PID 1 DERIVATIVE
MESSAGE
LIMIT: 10
PID 1 MAX:
MESSAGE
10
PID 1 MIN:
MESSAGE
10
PID 1 Tmin:
MESSAGE
500 ms
PID 1 DEAD TIME:
MESSAGE
1.00 sec
PID 1 BLK:
MESSAGE
Off
PID 1
MESSAGE
TARGET: Self-reset
PID 1
MESSAGE
EVENTS: Disabled
F35 Multiple Feeder Protection System
PID 1(4) REGULATOR
Range: Enabled, Disabled
Range: 0.05 to 30.00 s in steps of 0.01
Range: Off, any FlexAnalog parameter
Range: -99999.99 to 99999.99 in steps of 0.01
0.00
Range: Off, any FlexAnalog parameter
Range: 0.01 to 100.00 in steps of 0.01
Range: 0.01 to 1.00 in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: Enabled, Disabled
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 1 to 20 in steps of 1
Range: -10000 to 10000 in steps of 1
Range: -10000 to 10000 in steps of 1
Range: 100 to 1000 ms in steps of 1
Range: 1 to 20 s in steps of 1
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Enabled, Disabled
5 SETTINGS