GE UR F35 Series Instruction Manual page 461

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

APPENDIX B
Table B–10: MODBUS MEMORY MAP (Sheet 31 of 60)
ADDR
REGISTER NAME
Breaker Arcing Current Settings (Read/Write Setting) (6 modules)
7290
Breaker 1 Arcing Current Function
7291
Breaker 1 Arcing Current Source
7292
Breaker 1 Arcing Current Initiate A
7294
Breaker 1 Arcing Current Initiate B
7296
Breaker 1 Arcing Current Initiate C
7298
Breaker 1 Arcing Current Delay
7299
Breaker 1 Arcing Current Limit
729A
Breaker 1 Arcing Current Block
729C
Breaker 1 Arcing Current Target
729D
Breaker 1 Arcing Current Events
729E
...Repeated for Breaker 2 Arcing Current
72AC
...Repeated for Breaker 3 Arcing Current
72BA
...Repeated for Breaker 4 Arcing Current
72C8
...Repeated for Breaker 5 Arcing Current
72D6
...Repeated for Breaker 6 Arcing Current
Disconnect (Breaker) Switch (Read/Write Setting) (24 modules)
74A0
Disconnect Switch 1 Function
74A1
Disconnect Switch 1 Name
74A4
Disconnect Switch 1 Mode
74A5
Disconnect Switch 1 Open
74A7
Disconnect Switch 1 Block Open
74A9
Disconnect Switch 1 Close
74AB
Disconnect Switch 1 Block Close
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
74B1
Disconnect Switch 1 Phase B Closed
74B3
Disconnect Switch 1 Phase B Opened
74B5
Disconnect Switch 1 Phase C Closed
74B7
Disconnect Switch 1 Phase C Opened
74B9
Disconnect Switch 1 Operate Time
74BA
Disconnect Switch 1 Alarm Delay
74BC
Disconnect Switch 1 Events
74BD
Reserved (2 items)
74BF
...Repeated for Disconnect Switch 2
74DE
...Repeated for Disconnect Switch 3
74FD
...Repeated for Disconnect Switch 4
751C
...Repeated for Disconnect Switch 5
753B
...Repeated for Disconnect Switch 6
755A
...Repeated for Disconnect Switch 7
7579
...Repeated for Disconnect Switch 8
7598
...Repeated for Disconnect Switch 9
75B7
...Repeated for Disconnect Switch 10
75D6
...Repeated for Disconnect Switch 11
75F5
...Repeated for Disconnect Switch 12
7614
...Repeated for Disconnect Switch 13
7633
...Repeated for Disconnect Switch 14
7652
...Repeated for Disconnect Switch 15
7671
...Repeated for Disconnect Switch 16
7690
...Repeated for Disconnect Switch 17
76AF
...Repeated for Disconnect Switch 18
76CE
...Repeated for Disconnect Switch 19
76ED
...Repeated for Disconnect Switch 20
770C
...Repeated for Disconnect Switch 21
GE Multilin
RANGE
0 to 1
0 to 5
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 50000
0 to 4294967295
0 to 2
0 to 1
0 to 1
---
0 to 1
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 65.535
0 to 65.535
0 to 1
---
F35 Multiple Feeder Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
2
kA
-cyc
1
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
---
F206
---
1
F157
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
---
1
F300
s
0.001
F001
s
0.001
F003
---
1
F102
---
---
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
0
0
0
0
1000
0
0 (Self-reset)
0 (Disabled)
B
0 (Disabled)
"SW 1"
0 (3-Pole)
0
0
0
0
0
0
0
0
0
0
70
0
0 (Disabled)
0
B-39

Advertisement

Table of Contents
loading

Table of Contents