B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 32 of 60)
ADDR
REGISTER NAME
772B
...Repeated for Disconnect Switch 22
774A
...Repeated for Disconnect Switch 23
7769
...Repeated for Disconnect Switch 24
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
7789
Thermal Protection 1 Source
778A
Thermal Protection 1 Base Current
778B
Thermal Protection 1 K Factor
778C
Thermal Protection 1 Trip Time Constant
778D
Thermal Protection 1 Reset Time Constant
B
778E
Thermal Protection 1 Minimum Reset Time
778F
Thermal Protection 1 Reset
7791
Thermal Protection 1 Block
7793
Thermal Protection 1 Target
7794
Thermal Protection 1 Events
7795
Reserved (2 items)
7797
Repeated for Thermal Protection 2
Broken Conductor Detection (Read/Write Settings) (6 modules)
77AA
Broken Conductor 1 Function
77AB
Broken Conductor 1 Source
77AC
Broken Conductor 1 I2/I1 Ratio
77AD
Broken Conductor 1 I1 Minimum
77AE
Broken Conductor 1 I1 Maximum
77AF
Broken Conductor 1 Pickup Delay
77B0
Broken Conductor 1 Block
77B2
Broken Conductor 1 Target
77B3
Broken Conductor 1 Events
77B4
Reserved (2 items)
77B6
...Repeated for Broken Conductor 2
77C2
...Repeated for Broken Conductor 3
77CE
...Repeated for Broken Conductor 4
77DA
...Repeated for Broken Conductor 5
77E6
...Repeated for Broken Conductor 6
Ohm Inputs (Read/Write Setting) (2 modules)
77F8
Ohm Inputs 1 Function
77F9
Ohm Inputs 1 ID
77FF
Ohm Inputs 1 Reserved (9 items)
7808
...Repeated for Ohm Inputs 2
Underfrequency (Read/Write Setting) (6 modules)
7A80
Underfrequency 1 Function
7A81
Underfrequency 1 Block
7A83
Underfrequency 1 Min Current
7A84
Underfrequency 1 Pickup
7A85
Underfrequency 1 Pickup Delay
7A86
Underfrequency 1 Reset Delay
7A87
Underfrequency 1 Source
7A88
Underfrequency 1 Events
7A89
Underfrequency 1 Target
7A8A
Underfrequency 1 Reserved (5 items)
7A8F
...Repeated for Underfrequency 2
7A9E
...Repeated for Underfrequency 3
7AAD
...Repeated for Underfrequency 4
7ABC
...Repeated for Underfrequency 5
7ACB
...Repeated for Underfrequency 6
B-40
RANGE
0 to 1
0 to 5
0.2 to 3
1 to 1.2
0 to 1000
0 to 1000
0 to 1000
0 to 4294967295
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
0 to 5
20 to 100
0.05 to 1
0.05 to 5
0 to 65.535
0 to 4294967295
0 to 2
0 to 1
---
0 to 1
---
0 to 65535
0 to 1
0 to 4294967295
0.1 to 1.25
20 to 65
0 to 65.535
0 to 65.535
0 to 5
0 to 1
0 to 2
0 to 1
F35 Multiple Feeder Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F102
---
1
F167
pu
0.01
F001
---
0.05
F001
min.
1
F001
min.
1
F001
min.
1
F001
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
1
F167
%
0.1
F001
pu
0.01
F001
pu
0.01
F001
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
---
F001
---
1
F102
---
---
F205
---
1
F001
---
1
F102
---
1
F300
pu
0.01
F001
Hz
0.01
F001
s
0.001
F001
s
0.001
F001
---
1
F167
---
1
F102
---
1
F109
---
1
F001
DEFAULT
0 (Disabled)
0 (SRC 1)
80
110
45
45
20
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
200
10
150
20000
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
"Ohm Ip 1 "
0
0 (Disabled)
0
10
5950
2000
2000
0 (SRC 1)
0 (Disabled)
0 (Self-reset)
0