5.2 PRODUCT SETUP
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
 XSWI
 CONFIGURATION
5
The
CLEAR XSWI1 OpCnt
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they are not usually be forwarded by net-
work routers. However, GOOSE messages may be forwarded by routers if the router has been configured for VLAN
functionality.
NOTE
j) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 WEB SERVER
 HTTP PROTOCOL
The F35 contains an embedded web server and is capable of transferring web pages to a web browser such as Internet
Explorer or Firefox. The web pages are organized as a series of menus that can be accessed starting at the F35 "Main
Menu". Web pages are available showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault
reports, and so on. First connect the UR and a computer to an Ethernet network, then enter the IP address of the F35 into
the "Address" box of the web browser.
When the port is set to 0, the change takes effect when the F35 is restarted.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
NOTE
those protocols.
5-44

COMMUNICATIONS
XSWI1 ST.LOC OPERAND
Off
XSWI2 ST.LOC OPERAND
MESSAGE
Off
XSWI3 ST.LOC OPERAND
MESSAGE
Off
XSWI24 ST.LOC OPERAND
MESSAGE
Off
CLEAR XSWI1 OpCnt:
MESSAGE
No
CLEAR XSWI2 OpCnt:
MESSAGE
No
CLEAR XSWI3 OpCnt:
MESSAGE
No
CLEAR XSWI24 OpCnt:
MESSAGE
No
setting represents the disconnect switch operating counter. As disconnect switches operate by

COMMUNICATIONS
HTTP TCP PORT
NUMBER:
F35 Multiple Feeder Protection System


IEC 61850 PROTOCOL
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes

WEB SERVER HTTP PROTOCOL
Range: 0 to 65535 in steps of 1
80
5 SETTINGS
XSWI CONFIGURATION