GE UR F35 Series Instruction Manual page 139

Multiple feeder protection system
Hide thumbs Also See for UR F35 Series:
Table of Contents

Advertisement

5 SETTINGS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Login: This setting is applicable for Local Authentication only. This setting allows a user to login with a specific role, see
descriptions below. For the Supervisor role, the "Supervisor Role" setting should be enabled.
Whenever a new role is logged in, the user is prompted with a display to enter a password. 20 alphanumeric characters are
acceptable as passwords.The UR device supports five roles. All roles have their corresponding passwords. The Observer
role is the only role that does not require a password.
The roles are defined as follows:
Administrator: Complete read and write access to all settings and commands. This role does not allow concurrent
access. This role has an operand to indicate when it is logged on.
Engineer: Complete read and write access to all settings and commands with the exception of configuring Security set-
tings and Firmware upgrades. This role does not allow concurrent access.
Operator: The Operator has read/write access to all settings under the command menu/section. This role does not
exist offline.
Supervisor: This is only an approving role. This role's authentication commits setting changes submitted by Administra-
tor or Engineer. The Supervisor role authenticates to unlock the UR relay for setting changes and not approve changes
after the fact. Only Supervisor can set the Settings and Firmware Lock in the Security Settings. This role also has the
ability to forcefully logoff any other role and clear the security event log. This role can also be disabled, but only
through a Supervisor authentication. When this role is disabled its permissions are assigned to the Administrator role.
Observer: This role has read only access to all UR settings. This role allows unlimited concurrent access but it has no
download access to any files on the device. Observer is the default role if no authentication has been done to the
device. This role displays as "None" on the front panel.
The Factory service role is not available and is intended for factory use only.
NOTE
c) LOCAL PASSWORDS
PATH: SETTINGS
PRODUCT SETUP
 CHANGE LOCAL
 PASSWORDS
MESSAGE
MESSAGE
The Change Local Passwords menu is shown on the front panel and Enervista on a successful login of Administrator role.
The "login setting" in this menu is similar to the login setting described in PATH: SETTINGS > PRODUCT SETUP > SECU-
RITY except for the factory role.
Passwords are stored in text format. No encryption is applied.
Notes:
NOTE
GE Multilin
 RESTORE DEFAULTS
 SUPERVISORY
SYSLOG IP ADDRESS:
0.0.0.0
SYSLOG PORT NUMBER:
514

SECURITY
CHANGE LOCAL PASSWORDS
LOGIN:
None
NEW PASSWORD:
CONFIRM PASSWORD:
F35 Multiple Feeder Protection System
5.2 PRODUCT SETUP
See page 5–16.
See page 5–16.
Range: 0.0.0.0, 255.255.255.255
Range: 1 to 65535
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
Range: 20 Alphanumeric Characters
5
5-15

Advertisement

Table of Contents
loading

Table of Contents