Installation; Operation; Performance Specifications; Hardware Specifications - Baldor VS1MX Installation & Operating Manual

Ac extreme duty microdrive
Table of Contents

Advertisement

E.2 Installation

1. Connect the RS485 communication line to RJ45 connector, (see Figure E-1).
2. Check the connections and turn ON the inverter.
3. Table E-1 documents the parameters within the VS1MX that are related to communications:
Number
P07
P35
P35
P35
4. Make connection to the master and other slave devices. The maximum number of drives that can be connected is 31.
Maximum length of communication line is 2300 ft (700m).
E.3 Operation
1. Remove all power from the VS1MX control.
2. Disconnect the motor load from the control (terminals U, V and W). (Do not connect the motor load until stable
communication between the master controller and the inverter are verified.)
3. Verify master controller and the inverter connections.
4. Turn ON the inverter.
5. Start the communications program on the master controller.
6. Verify proper communications and that the VS1MX is controlled as desired.
7. Remove all power from the VS1MX control.
8. Connect the motor load to the control (terminals U, V and W).
9. Turn ON the inverter.
10. Verify proper operation. See Troubleshooting at the end of this section to aid in resolving any remaining problems.
E.4 Performance Specifications
Communication Method
Transmission Form
Applicable inverter
Connectable drives
Transmission distance
E.5 Hardware Specifications

Installation

Power Supply
E-2 RS485/MODBUS Protocol
Table E-1 Communication Parameters
Name
Set to 3 or 4 for applications that require network control to start and stop the
Start/Stop Source
drive over the network.
Set to the desired Modbus-RTU address (note that each device on the
Drive Address
network must have a unique address).
Select the baud rate utilized by the master device on the network. All devices
Baud Rate
on the network must utilize the same baud rate.
Trip Enable Delay
Set to desired trip response to a loss of communications.
Table E-2 Communication Performance
Bus method, Multi drop Master/Slave architecture
VS1MX series
Max 31
Max. 2,300 ft (Repeater may be required for high noise environments.)
Table E-3 Communication Hardware
Use RJ45 connector on control (see Figure E-1)
Provided by isolated power from the inverter power supply
Comments
RS485 Hardware specification, MODBUS protocol
MN762