Baldor VS1MX Installation & Operating Manual page 35

Ac extreme duty microdrive
Table of Contents

Advertisement

Number
(Display Level)
Analog Input Offset
P-30
P-31
Brake After Stop
Brake Before Start
P-32
P-33
Decel2
Fast Stop
P-34
Brake Chopper Enable
MN762
Table 7-1 Parameter Descriptions Continued
Name
Value Range, Description and Preset Value
Range: -500.0 to 500.0%
Preset: 0.0
Amount of offset for analog input level.
Resolution of 0.1%.
Range: 0 to 60.0 seconds
Preset: 0.0
Sets the amount of time DC injection braking is applied during stop when zero
speed is reached. (P-31=0, no DC Brake is applied). The amount of braking is set
in P-18 - Voltage Boost. See also P-18, P-32.
Range: 0 or 1
Preset: 0
0: The drive accelerates to speed without delay.
1: Applies DC braking when run command is issued.
The amount of time is set in P-31 and the amount of braking in P-18. The drive
will then accelerate. DC braking may be applied after run command is issued.
See also P-18, P-31.
Range: 0 to 25
Preset: 0.00
Sets a second Decel time.
P-33 is used if the drive input power is lost or fast stop mode is selected; P-09=0
or 2. Fast stop may also be enabled by setting P-08 =12 and opening Digital
Input 2.
When P-09 = 2 and P-33 = 0, activating the fast stop disables the drive without
braking, effectively coasting to a stop.
See also P-08, P-09.
Range: 0 to 2
Preset: 0
0: Disabled
1: Enabled with Software protection for standard brake resistors (200W)
2: Enabled without s/w protection.
When enabled, the VS1MX software monitors bus voltage and turns On/Off
braking as shown here.
Drive Voltage
Brake Turn Off
Rating
Level
240VAC
378VDC
460VAC
756VDC
Brake Turn On
Level
390VDC
780VDC
Parameter Descriptions 7-7