B.1 Parameters Sorted by Parameter Number
Param
Access
#
P00
RO
P01
RW
P02
RW
P03
RW
Motor Rated Frequency
P04
RW
P05
RW
Minimum Output Speed
P06
RW
Maximum Output Speed
P07
RW
P08
RW
P09
RW
P10
RW
P11
RW
P12
RW
P13
RW
P14
RW
P15
RW
P16
RW
Speed Reference Scaling
P17
RW
P18
RW
P19
RW
P20
RO
P21
RW
P22
RW
P23
RW
Display Speed Scale Factor
MN762
Table B-1 Parameters Sorted by Parameter Number
Parameter Name
Read Only Parameters
Motor Rated Volts
Motor Rated Current
Motor Rated Speed
Start/Stop Source
Operating Mode
Stop Mode
Accel Time
Decel Time
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Analog Input Format
(Analog In 1)
Voltage Boost
Energy Savings
Trip Log
PWM Frequency
Relay Output
Description (Range)
1-20
0, 20-250VAC or 0, 20-500VAC
25-100%
25 to 500 Hz
0 to 30000 RPM
0.0 to P06 (max 500.0Hz)
P05 to 5*P03 (max 500Hz)
0- Terminal Strip
1- Keypad FWD
2- Keypad bi-directional
3- MODBUS with accel / decel ramps
4- MODBUS with accel / decel ramp adjustment
5- User PI with external FDBK
6- User PI control Analog Input
0-12
0: Ramp to stop
1: Coast to stop
2: Ramp to stop (fast stop)
0 to 600 seconds
0 to 600 seconds
-P06 to P06
-P06 to P06
-P06 to P06
-P06 to P06
0 to 500%
0-10V, 0-20mA, 4-20mA, 20-4mA
0.0 to 20.0%
0: Disabled
1: Enabled
Last Four Trips Stored
4 to 32 kHz
0: Drive enabled
1: Drive healthy
2: Motor at target speed
3: Drive tripped
4: Motor speed >= limit
5: Motor current >= limit
6: Motor speed < limit
7: Motor current < limit
Custom scaling factor used only if P-04 > 0
Appendix B

Parameter Tables

Factory
Setting
0
CALC
60
0
0.0
60.0
0
0
0
5.0
5.0
0.0
0.0
0.0
0.0
100.0
u 0-10
CALC
0
16
1
0.000
Parameter Tables B-1
User
Setting

Hide quick links: