Factory Settings - ABB ttr200 Operating Instruction

Rail-mount temperature transmitter
Hide thumbs Also See for ttr200:
Table of Contents

Advertisement

DTM menu path, parameters
<Device> / <Configuration>
<Sensor / Reference junction>
<Sensor / Reference junction
temperature>
<Device > / <Parameterize>
<Measuring range of PV / unit>
<Measuring range of PV / lower
range value>
<Measuring range of PV / upper
range value>
<Current output / damping>
<Current output / output upon
error > (overrange)
<Current output / output upon
error > (underrange)
<Device> / <Maintenance>
<Poll address / TAG>
(HART TAG)
<Poll address / TAG>
(Address (Multidrop))
<Adjustment> (Set lower range
value)
<Adjustment> (Set upper range
value)
<Adjustment /DAC adjustment
fixed for zero at 4 mA>
<Adjustment /DAC adjustment
fixed for amplification at 20 mA>
<Device> <Simulation>
9.5

Factory settings

The transmitter is configured at the factory. The table below contains the relevant parameter values.
Menu
Device Setup
Process Alarm
Change from one to two columns
Description
— Internal: use of the internal reference junction of the transmitter when using a thermocouple/compensating cable
(relevant for all thermocouples except for type B)
— External - fixed: transfer of thermal cable/compensating cable via copper material at constant thermostat
temperature
— Without: no cold junction
— Relevant for external reference junction, specification of constant external reference junction temperature
Value range: -50 ... 100 °C
Selects the physical unit for the sensor measuring signal
Units: °C, °F, °R, K, mV, Ω, mA
Defines the value for 4 mA (adjustable)
Defines the value for 20 mA (adjustable)
Configurable τ 63% output signal damping value
Value range: 0 ... 100 s
Generates a high alarm signal in the event of a sensor or device error; can be configured 20 ... 23.6 mA.
— Standard 22 mA
Generates a low alarm signal when sensor or device errors occur; can be configured from 3.5 ... 4 mA
Defines the HART TAG name.
— 8 characters, alphanumeric
Specifies the communication type
— Address = 0 conforms to HART operating mode: point-to-point communication, 4 ... 20 mA output signal
— Address = 1 ... 15 conforms to HART multidrop operating mode output signal 3.6 mA, only the digital HART
readings are available
Temperature correction for specified / simulated sensor LRV value to desired LRV temperature value
— Set Trim low or lower range value > OK
Temperature correction for specified / simulated sensor URV value to desired URV temperature value
— Set Trim high or upper range value > OK
Output signal correction for specified / simulated sensor LRV value to 4.000 mA set point
— Analog current measurement value input min. 3.5 ... max. 4.5 mA
Output signal correction for specified / simulated sensor URV value to 20.000 mA set point
— Analog current measurement value input min. 19.5 ... max. 20.5 mA
Output signal simulation corresponding to the value specified
— Value range: 3.5 ... 23.6 mA
Designation
Write protection
Input
Parameter
-
Sensor Type
R-Connection
Measured Range Begin
Measured Range End
Engineering Unit
Damping
Fault signaling
Factory setting
No
Pt100 (IEC60751)
Three-wire circuit
0
100
Degrees C
Off
Overrange 22 mA
TTR200 | OI/TTR200-EN Rev. B 19