Audible Alarm; Troubleshooting; Table 7-2: Audible Alarm Description; Table 7-3 Troubleshooting Table - Emerson GXT4-5000RT230 User Manual

Liebert gxt4 230 v, 5000 va – 10,000 va
Hide thumbs Also See for GXT4-5000RT230:
Table of Contents

Advertisement

Troubleshooting

7.1.2

Audible Alarm

An audible alarm will sound in conjunction with the visual indicators to indicate a change in UPS operating
status. The audible alarm will sound as described in Table 7-2.
Battery discharge
Low battery
UPS fault, load on bypass
UPS fault, no power to load
Overload
Battery replacement
Battery loss
Wiring problem (loss of proper grounding for UPS)
Bypass reminder
7.2 Troubleshooting
In the event of an issue with the UPS, refer to Table 7-3 to determine the cause and solution. If the fault
persists, contact Emerson
Problem
UPS is short-circuited or
overloaded
UPS fails to start
Batteries are not charged
enough or not connected
UPS is not plugged in
Battery indicator
UPS input protection fuse has
is illuminated
blown/opened
Mains power is out of tolerance
Batteries are not fully charged
UPS has
reduced battery
UPS is overloaded
backup time
Batteries may not be able to
hold a full charge due to age
Battery indicator
Battery source is not available;
is flashing.
continuous horn.
Because the voltage or
Bypass indicator
frequency is outside acceptable
is flashing.
limits, the bypass is disabled.
®
Liebert
GXT4
User Manual
Table 7-2
Audible alarm description
Condition
®
Channel Support.
Table 7-3
Troubleshooting table
Cause
Ensure UPS is Off. Disconnect all loads and ensure nothing is lodged in
output receptacles. Ensure loads are not defective or shorted internally.
Check to ensure the internal battery is connected. If it is not, make the
connection and try to start the unit. If the battery is connected, leave the
UPS connected to input power for 24 hours to recharge batteries, then try
to start the unit.
UPS is operating from battery mode. Ensure UPS is securely plugged
into the wall receptacle.
UPS is operating from battery mode. Save data and close applications.
Replace UPS input fuse, then restart UPS.
UPS is operating from battery mode. Save data and close applications.
Ensure mains supply voltage is within acceptable limits for UPS.
Keep UPS plugged in continuously at least 24 hours to recharge
batteries.
Check load level indicator and reduce the load on the UPS.
Replace batteries. Contact your local dealer, Emerson representative or
Emerson Channel Support for replacement battery kit.
Check battery connections, completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS is running, it will be
detected when the next battery test is performed.
The AC input powers the PFC input and serves as the bypass source. If
the AC is present but the voltage or frequency exceeds the acceptable
range for safe operation with a load, the bypass will be disabled and this
indicator will flash, indicating that the bypass is unavailable.
Alarm
Half-second beep every 10 seconds
Two half-second beeps every 5 seconds
1-second beep every 4 seconds
Continuous
Half-second beep every half second
2-second beep every 2 minutes
Continuous
Continuous
1-second beep every 60 seconds
Solution
50