Specifying application parameters (P1080)
• Set the minimum frequency under parameter MIN RPM.
• Press OK (Parameter MIN RPM).
• Change by pressing UP or DOWN.
• Press OK to confirm.
OK
• Set the ramping-up time under parameter RAMP UP for acceleration time to maximum
frequency (P1120).
• Set the ramping-down time under parameter RAMP DWN for time until standstill (P1121).
OK
OK
The values are displayed in seconds. In both cases, the times indicated
should not be too short, because this might result in an alarm.
Finishing
• Press OK when the BOP-2 shows FINISH.
• Confirm by using the UP or DOWN button to select YES and press
OK again.
OK
You have now reached the end of the quick commissioning.
The inverter can now be turned on using digital input DI 0.
The setpoint source is specified as the potentiometer.
OK
OK
OK
OK
Changing the value digit by digit is
possible by pressing the OK button
longer than 2 seconds. After releas-
ing the button, you can change any
single digit by using the buttons OK
(move to next digit), ESC (move to
previous digit), UP (increase value),
and DOWN (decrease value).
Refer to the "Parameter Manual:
Control Units – CU240E/B-2" for a
description of the control modes
and their corresponding parameter
settings at http://support.automa-
tion.siemens.com/WW/view/
en/30563628/133300
Note
Note