Motor data identification

After entering the motor data, the wizards asks you to activate the motor data identification.
Motor ID is recommended for a live verification and optimization of the data that you have
entered. The motor data identification initiates a "measurement" of the connected motor. In the
process, the data previously calculated in the inverter is compared to the actual motor data and
they are adapted to one another.
Starting motor data identification (P1900)
• Press OK to modify the displayed parameter value.
• Change the displayed value to 1 by pressing UP.
• The display will automatically display the next parameter in the commissioning sequence.
OK
Motor identification will not start until the basic commissioning sequence has been
completed.
• Start the motor manually (by using digital input DI 0 or by activating the HAND mode
and starting the drive using the ON button).
• The measuring process is set in motion.
• When finished, the motor switches off.
• BOP-2 indicates that the measured values are now being converted into data.
HAND
AUTO
The inverter can now be turned on using digital input DI 0. The setpoint
source is specified as the potentiometer.
Caution: the motor can rotate
slightly in the process.