Testing the application

Now check to see how the motor reacts to the digital inputs being actuated. To do so, flip switch
DI 0 (start the motor) and DI 3 (activate the first fixed frequency). The motor starts. Now use the
Basic Operator Panel 2 to enter the menu function MONITORING by pressing OK. You'll see that
the motor setpoint has been set to 300 1/min and that the motor is accelerating/running at the
speed of 300 1/min. Now also flip switch DI 5. You'll see that the speed of 300 1/min and 600 1/
min are added. The motor runs at a speed of 900 1/min now.
Monitoring the fixed frequencies
• Press ESC.
• Navigate with the menu bar to the menu function MONITORING.
• Press OK.
ESC
The Basic Operator Panel 2 can also be used to make a variety of other adjustments to your ap-
plication. An overview of the parameters can be found in the "Operating Instructions: Control
Units CU240E".
Saving and restoring a parameter set
Saving parameter set from inverter in the BOP-2
• Navigate to the menu function EXTRAS and press OK.
• Push the DOWN button until TO BOP appears and press OK.
OK
OK
Copying parameter set from BOP-2 in the inverter
• Navigate to the menu EXTRAS and press OK.
• Push the DOWN button until FROM BOP appears and press OK.
OK
OK
OK
OK OK
OK OK
The BOP-2 can be mounted or re-
moved at any time. The device is not
necessary for ongoing operation.
Note