Menu 5.15.0 [S] OU communication
Readings regarding any communication errors can be made in
the sub-menus to this menu.
Menu 5.15.1 [S] Com. error rate
Shows the percentage of incorrect communications with
outdoor unit since start-up.
Menu 5.15.2 [S] Com. errors
Shows the total number of incorrect communications with
outdoor unit since start-up.
Menu 5.15.3 [S] Reset com. errors
Select "Yes" here to reset the counters in menu 5.15.1 and
5.15.2. The settings returns to "No" once the action has been
carried out.
Setting range: Yes, No
Menu 5.15.4 [S] Return
Return to Menu 5.15.0.
Menu 5.16 [N] Return
Return to Menu 5.0.
6.0 [N] Room temperature*
Requires accessory and activation in Menu 9.3.6.
*
Menu 6.1 [U] Room compensation
A factor is selected here that determines how much the
calculated supply temperature is affected by the difference
between the room temperature and the set room temperature. A
higher value gives a greater change.
Setting range: 0 – 10.0
Default value: 2.0
Menu 6.2 [U] Heating system
You select here whether the room sensor is Valid for heating
system 1 (menu 2.0) and/or heating system 2 (menu 3.0).
Setting range: Off, System 1, System 2, System 1+2
Default value: Off
Menu 6.3 [N] Room temp. setpoint
The desired room temperature is shown here.
Setting range: 10 – 30 °C
Menu 6.4 [U] Room temp avg. 1min
Shows the average room temperature over the last minute.
Menu 6.5 [U] Room integrator time
Select the integration time for room control here.
Setting range: 0 – 120
Default value: Off
Menu 6.6 [N] Return
Return to Menu 6.0.
- 98 -
'10 • HM-T-149
Control
Control