Mitsubishi HMA100V Technical Manual page 200

Air to water heat pump
Hide thumbs Also See for HMA100V:
Table of Contents

Advertisement

FDCW140VNX
Compressor (CM)
2. Untie the strings and remove
the top and side insulations
3 Cut off the strap and pull
out the sensor (Tho-D)
4. Remove the terminal cover
5. Disconnect the fasten
connectors from compressor.
U: Red cable
V: White cable
W: Blue cable
6. Remove the crankcase
heater
7. Unscrew and disconnect
the grounding cable
8. Loosen 3 nuts of
compressor fixing bolts
9. Disconnect the pipes for
suction and discharge gas
10. Remove the compressor
Terminal cover
Suction gas pipe
Discharge gas pipe
- 199 -
'10 • HM-T-149
Component replacement
Tho-D
Insulation (top section)
Outer insulations (side section)
Inner insulations (side section)
Crankcase heater
Screw for groundin cable
3 nuts of compressor
fixing bolts
Service

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents