FDCW100VNX
Compressor (CM)
4. Remove the top insulation
5. Remove the terminal cover
6. Disconnect the fasten terminal
connectors from compressor.
U: Red cable
V: White cable
W: Blue cable
7. Cut off the strap and pull
out the sensor (Tho-D)
8. Remove the control unit for
easy replacement work of
compressor according to
following procedure.
1) Disconnect all connectors
shown in the photo
2) Cut off the straps
3) Unscrew and disconnect
the grounding cable
4) Loosen the screws shown
in the photo.
5) Remove the control unit.
Note: Be sure to do above
work after elapsing
3 minutes from
power OFF.
Top Insulation
Tho-D
2 straps
CNH
CNEEV2
CNS
CNEEV1
CNR
CNFAN1
2 straps
Screws
- 192 -
Component replacement
Terminal cove r
Fasten terminal
CNB
Screw for
Strap
CNTH
grounding
Screws
'10 • HM-T-149
Service
CNPS