Menu 9.5.7 [S] Program version
The current program software version in indoor unit is shown
here.
Menu 9.5.8 [S] 106-card version
The communication PCB version number is shown here (AA23).
Menu 9.5.9 [S] Display version
The display version number is shown here.
Menu 9.5.10 [S] Relay card version
The relay PCB version number is shown here.
Menu 9.5.11 [S] Lowest supply temp.
The minimum supply water temperature since start-up is
shown here.
Menu 9.5.12 [S] Percent runtime
The compressor's running time percentage.
Menu 9.5.13 [S] Period
Period counter for switching between hot water and heating/
cooling.
Menu 9.5.14 [S] Run status
Shows the current operating status of outdoor unit
The display can show: Off, Hot water, Heating, Cooling,
Defrost, Oil return or XHW.
Menu 9.5.15 [S] Run status last
Shows the previous operating status for outdoor unit
The display can show: Off, Hot water, Heating, Cooling,
Defrost, Oil return or XHW.
Menu 9.5.16 [S] Run status time
The time since the last operating status change.
Menu 9.5.17 [S] Return
Return to Menu 9.5.0.
Menu 9.6.0 [S] Heat reg. settings
Settings regarding the heating regulator can be made in the sub-
menus to this menu.
Menu 9.6.1 [S] CompFreq
The current target frequency of the compressor is shown here.
Setting the target frequency during manual control of the
compressor is activated in Menu 9.6.2.
FDCW71
Setting range(Hz)
20 – 118
Menu 9.6.2 [S] Manual CompFreq
Select "On" to control the compressor frequency manually in
Menu 9.6.1.
Setting range: Off, On
FDCW100 FDCW140
20 – 85
20 – 120
- 105 -
Default value: Off
Menu 9.6.3 [S] Max deltaF
The parameter for the heat regulator's max change of the target
compressor frequency is selected here.
Setting range: 1 – 10 Hz
Default value: 3 Hz
Menu 9.6.4 [S] CompFreq regP
Select P part for heat regulator.
Setting range: 1 – 60 Hz
Default value: 5
Menu 9.6.5 [S] Time min freq start
Select here the time that the compressor is to run at min speed,
after start connecting to the climate system.
Setting range: 10 – 120 min
Default value: 70 min
Menu 9.6.6 [S] Time min freq heat
Select here the time that the compressor is to run at fixed
frequency after shifting to heating. The compressor then runs
at min frequency or at the frequency it had before hot water
charging.
Setting range: 3 – 60 min
Default value: 3 min
Menu 9.6.7 [S] Max diff flow-cFlow
You can set the maximum overshoot of the supply temperature
from the target. Max. deviation of supply temperature is
controlled by this setting regardless of degree minutes value.
Setting range: 2.0 – 10.0 °C
Default value: 4.0 °C
Menu 9.6.8 [S] CompFreq GMz
Here you select a value for the dynamic in the degree minute
regulator.
Setting range: 95 – 127
Default value: 126
Menu 9.6.9 [S] Return
Return to Menu 9.6.0.
Menu 9.7 [S] Reset alarm
Select "Yes" here to reset/acknowledge alarms in indoor unit. The
settings returns to "No" once the action has been carried out.
Setting range: Yes, No
Menu 9.8.0 [S] Alarm log
The alarm logs with the last 4 alarms are shown in the sub-
menus of this menu.
Menu 9.8.1.0 – 9.8.4.0 [S] Log 1 – Log 4
The alarm logs are shown in the sub-menus of this menu. Log
1 is the last alarm, log 2 the next to last, etc.