Mitsubishi HMA100V Technical Manual page 283

Air to water heat pump
Hide thumbs Also See for HMA100V:
Table of Contents

Advertisement

Connecting hot water heater / buffer vessel (Page 8 in installation manual)
For MT500,install joints and relevant components as illustrated before connecting pipes.
<T connection with Mamometer>
Fasten it on XL24 so that the Mamometer comes on top.
T connection
Pipe connection
Pipe connections are made at the location as illustrated.
It is necessary to connect hot water tank or buffer vessel even if hot water supply is not necessary.
MT500
XL4
(To hot domestic water)
XL24
(From XL21)
XL3
(From cold
domestic water)
XL23
(To XL22)
For MT500,remove handing rod on top after installation and plug the hole with Isolation plug attached.
Connection of external heat source (Page 9 in installation manual)
MT500
Connect an external heat source such as gas or oil boiler to (XL8)(in) and (XL9)(out) on tank
unit(dimension G1 internal).
Remove the insulation lid which covers the port XL8 and XL9, and attach Cover on the edge of insulation
for better appearance.
Refer to the dimension drawing for connecting part XL8 and XL9 in this sheet.
For external heat source controlled by the indoor unit, disconnect the sensor on BT19, connect the
attached sensor as supplied parts on the same terminal instead and put it on BT24. It is recommended to
apply thermal silicone paste on the sensor element for better measurement.
For external heat source controlled independently, put the temperature sensor of it on BT24 to control it
appropriately.
<X connection>
1) Fasten it on XL23 so that the pipe for Ball valve is downwards.
2) Fasten Ball valve on the bottom pipe.
3) Fasten Safety valve on the side pipe so that drain outlet is downwards.
X-connection
To Tank (XL23)
Safety valve
Ball valve
HT30
Hanging rod
BT19
XL8
BT24
XL9
Electrical components (Tank) (Page 13 in installation manual)
MT500
FD1-BT30
X101
X100
Explanation
Symbol
Contents
X100
Terminal block, incoming supply to tank
X101
Terminal block, sensor from indoor unit
BT30
Thermostat, standby mode
FD1
Temperature limiter
Connection between indoor unit and tank (Page 14 in installation manual)
HT30
Connect the terminal as shown in the following figure.
It is not necessary to connect any wiring on the terminal No13 and No14 on AA22-X4.
HT30
Hydrobox HMS140V
sensor cable
-X100
power cable
-X4
1
2
sensor cable
-X101
AA22-X4
Venting the climate system (Page 19 in installation manual)
1. Vent tank unit through the air vent valve (QM20) and the rest of the heating system
through the relevant venting valves.
2. Open the valve to expansion vessel when air vent is completed.
3. After opening the valve, vent indoor unit through venting valve on indoor unit to
bleed rest of air completely.
Keep topping up and venting until all air has been removed and the correct pressure
has been obtained.
Commissioning (Page 19 in installation manual)
HT30
Indoor unit
7. Select "Service" in menu 8.1.1.
Set operating mode to "No HW" in menu 9.3.14.
HT30
X100 X101
Scale length of
conductor (mm)
13
9
16
15
14
13
PSB012D983
A