Manual shunting
When indoor unit is set to emergency mode
switch SF, the heating control system is not in operation, and
is why manual shunt operation is required.
1.To change a position of valve, depress a button
and lock it by pressing a hock shown in the photo.
2.Turn the mixing valve to the desired position by hand.
3.When recovered, press a button to unhook, so that the
valve is controlled by a system.
In the emergency mode, the valve position should be set as follows
<HMA100V, HMA100VM>
QM30
QM31
QN11
<HMS140V>
QN11
QM30
QM31
on the main
button
<Valve position of emergency mode>
QM30
<Valve position of emergency mode>
QM31
- 60 -
Indoor unit installation
hook
QM31
QN11
QN11
QM30
'10 • HM-T-149A
Installation
30