Data Storage; Trend Monitoring With Drive Window; Sending A Value - ABB ACS 600 User Manual

Aca 635 igbt supply sections (isu) 260 to 4728 kva
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Chapter 8 – Parameters

19 Data Storage

Trend Monitoring with
Drive Window
APC2, AC80
A
A = a value assigned from overriding system to drive control

Sending a value

APC2, AC80
B
B = a value assigned for overriding system application
8-14
Parameters of this group are storages for receiving information from or
sending it to an overriding system. The parameters are unconnected.
They can be used for linking, testing and commissioning purposes.
Example 1.
Address of data set 14 index 2 is 90.08. For monitoring a signal
assigned for drive control from data set 14 index 2 (data word 14.2) by
DriveWindow follow the steps below.
3. Set Parameter 90.08 D SET 14 VAL 2 to 1901 (denoting Parameter
19.01).
4. Set DriveWindow monitoring channel to read Parameter 19.01.
PC element
ACSRX
Data set 14
Index: 1
Index: 2
Index: 3
Example 1.
To send a value to overriding system data set 15 index 2, set
Parameter 92.08 D SET 15 VAL 2 to 1902 by a CDP 312 Control Panel
or DriveWindow.
PC element
ACSRX
Data set 15
Index: 1
Index: 2
Index: 3
NAMC-xx
Data set table
Data
Address
Index
set
Assignment
.
.
of Data set
.
.
Group Index
1
14
90
08
2
3
.
.
.
.
.
.
NAMC-xx
Data set table
Data
Index
Address
set
Assignment
.
.
of Data set
.
.
Group Index
1
15
92
08
2
3
.
.
.
.
.
.
PC
Drive Window
For
DriveWindow
Parameter
PC Tool
table
19.01
PC
Drive Window
From
DriveWindow
Parameter
PC Tool
table
19.02
ACA 635 IGBT Supply Sections
19.01
19.02