98 Option Modules

Code Parameter
98
OPTION
MODULES
98.01 COMMAND SEL
98.02 COMM MODULE I NO
ACA 635 IGBT Supply Sections
T
Default
Alternative
y
Settings
p
( ) Fieldbus
e
Equivalent
B I/O
(0) MCW
(1) I/O
(1) NO
(2) FBA DSET1
(3) FBA DSET10
(4) INVERTER
Description
This parameter selects the control command
interface(s).
The ISU control program reads the control commands
via a serial link and through the digital input terminals.
The ISU control program reads the control commands
through the digital input terminals.
This parameter defines the control mode and place in
the REMOTE mode.
The drive is controlled using I/O: DI2
The drive is controlled through the communication link
(CH0) using datasets 1 and 2. This is a typical setting
for use with a fieldbus adapter module.
The drive is controlled through the communication link
(CH0) using datasets 10 to 33. (for example APC2,
AC 70, AC80, NPBA-02, NCSA-01)
Not in use
Chapter 8 – Parameters