Led Panel Control - ABB ACS 600 User Manual

Aca 635 igbt supply sections (isu) 260 to 4728 kva
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

18 LED Panel Control

Code Parameter
18
LED PANEL
CTRL
18.01 LED PANEL
OUTPUT
18.02 SCALE PANEL
ACA 635 IGBT Supply Sections
T
Default
Range
y
p
e
I 109
0...30000
R 100
0...65536
Description
The NLMD-01 Monitoring Display has a LED bar
to show an absolute real type value:
0
50
100
150 %
.
The source and the scale of the display signal
are defined by this parameter group.
Note: If NLMD -01 and CDP 312 Control Panel
are used together, Actual Signal 1.26 LED
PANEL OUTPUT must be the first signal in
CDP 312 Actual Signal Display Mode. Otherwise
the NLMD-01 LED bar display will show an
incorrect value.
Signal source selection for the NLMD-01
Monitoring Display.
Example: To link Par. 1.09 POWER to the
display set Parameter 18.01 to value 109.
Scaling factor for the NLMD-01 Monitoring
Display.
Example: Par. 1.05 FREQUENCY is linked to
Parameter 18.01. The frequency is 50 Hz (= 100
·
50 = 5000 as integer scaled). Value 5000 of
Parameter 18.02 gives 100% display on the
NLMD-01.
Chapter 8 – Parameters
Integer
Scaling
1 = 1
1 = 1
8-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents