7 Control Word

8 Status Word

ACA 635 IGBT Supply Sections
Parameter 7.01 is the control word of the line converter. The control
word is a 16-bit packed boolean word displayed as a hex value and
updated at 10 ms intervals.
Parameter 7.01 MAIN CTRL WORD (Control word of the line converter)
Bit
Name
0
ON
OFF
1, 2
3
START
4...6
7
RESET
8...15
This parameter is a 16-bit packed boolean word displayed as a hex
value and updated at 4 ms intervals.
Parameter 8.01 MAIN STATUS WORD (Status signals of the line converter)
Bit
Name
0
RDY_ON
1
RDY_RUN
2
RDY_REF
3
TRIPPED
4, 5, 6
7
ALARM
8
MODULATING
9
REMOTE
10
NET OK
11
12, 13
14
CHARGING
15
Value
0 Þ 1 Starts charging
0
Opens main contactor
0
Not in use
1
Starts modulation
0
Stops modulation
0
Not in use
0 Þ 1 Makes a reset
0
0
Not in use
Value
1
Ready to switch on = no fault
0
Not ready to switch on = fault
1
Ready to operate = DC bus charged
0
Not ready to operate
1
Operation enabled
0
1
Fault
0
No fault
Not in use
1
Warning
0
No Warning
1
Line converter modulates.
0
Line converter not modulating
1
Drive control location: REMOTE
0
Drive control location: LOCAL
1
Network voltage is OK.
0
Network voltage is lost.
Not in use
Not in use
1
Charging contactor closed
0
Charging contactor open
Not in use
Chapter 8 – Parameters
Description
STATE/Description
8-5