Direct Marketer Interface (Unit Id = 200) - SMA SUNNY TRIPOWER 60 Technical Information

Sunspec modbus interface
Hide thumbs Also See for SUNNY TRIPOWER 60:
Table of Contents

Advertisement

SMA Solar Technology AG
26
5.4

Direct Marketer Interface (Unit ID = 200)

The individual registers are described in the following table.
5.4.1
Table C 001 (Common Model)
Description/Number Code(s)
Specified output limitation through direct marketer.
Percentage value regarding the maximum active power of
1
system (Reg. 6) with two decimal places. A value of 10000
corresponds to 100%. A value of 0x8000 (NaN) shows that
no value has been specified. Valid values from 0 to 10000.
Manual output limitation that has been set via SunSpec Mod-
bus.
2
Percentage value regarding the maximum active power of
system (Reg. 6) with two decimal places. A value of 10000
corresponds to 100%.
Output limitation through the electric utility company that has
been set via the IO box.
Percentage value regarding the maximum active power of
3
system (Reg. 6) with two decimal places. A value of 10000
corresponds to 100%. A value of 0x8000 (NaN) shows that
no value has been specified.
Minimum of all output limitations. The nominal PV system power
is derated to this value.
4
Percentage value regarding the maximum active power of the
system with two decimal places. A value of 10000 corresponds
to 100%.
Currently, the active power of the system is shown in kW with
one decimal place.
5
A value of 600 corresponds to 60.0 kW.
Technical Information
273 (warning)
STP60 SunSpec Modbus Profile – Assignment Tables
1
1
1
1
1
STP60-SunSpec_Modbus-TI-en-12
uint16
RW
uint16
RO
uint16
RO
uint16
RO
uint16
RO
45