SMA SUNNY TRIPOWER 60 Installation Manual

SMA SUNNY TRIPOWER 60 Installation Manual

Hide thumbs Also See for SUNNY TRIPOWER 60:

Advertisement

Installation Manual
SUNNY TRIPOWER 60
STP60-JP-10-IA-en-11 | Version 1.1

Advertisement

Table of Contents
loading

Summary of Contents for SMA SUNNY TRIPOWER 60

  • Page 1 Installation Manual SUNNY TRIPOWER 60 STP60-JP-10-IA-en-11 | Version 1.1...
  • Page 2 Legal Provisions The information contained in these documents is the property of SMA Solar Technology AG. Any publication, whether in whole or in part, requires prior written approval by SMA Solar Technology AG. Internal reproduction used solely for the purpose of product evaluation or other proper use is allowed and does not require prior approval.
  • Page 3: Table Of Contents

    SMA Solar Technology AG Table of Contents Table of Contents 1 Introduction......... . 7 1.1 System Overview .
  • Page 4 Table of Contents SMA Solar Technology AG 4.2 Maintenance ......... . . 29 5 Technical Data .
  • Page 5 SMA Solar Technology AG   Nomenclature General Safety Complete designation Designation in this document This manual contains important instructions that must be Sunny Tripower 60 Inverter, product followed during installation and maintenance of the SMA Digital I/O Box I/O Box inverter.
  • Page 6   SMA Solar Technology AG INFORMATION The PV load-break switch can be secured in the "Off" All persons responsible for the installation and position using a padlock. maintenance of inverters must be: • Trained and authorized in general safety rules for work on electric equipment.
  • Page 7: Introduction

    All work on the product must be • SMA Inverter Manager carried out by qualified persons only. The SMA Inverter Manager is always required for the Danger operation of the inverter. Up to 42 inverters can be This symbol indicates that the inverter connection to each SMA Inverter Manager.
  • Page 8: System Overview

    You can also request these from the establishing communication. supplier of the inverter. • Installation manual for the SMA Inverter Manager and the I/O Box - information necessary for commissioning and for establishing communication. • Service manual for replacing the fan – for information required to replace a fan.
  • Page 9 SMA Solar Technology AG 1  Introduction Abbreviation Description P is the symbol for active power and is measured in Watts (W). Printed circuit board Point of Common Coupling - point of interconnection The point on the public electricity network to which other customers are, or could be, connected.
  • Page 10: Unpacking

    The LCS-Tool must be installed on a local PC drive. The safely and when seeking customer support from the PC must be connected to the system network of the SMA Service Line. You will find the following information on SMA Inverter Manager. For setup via the LCS-Tool, the type label: refer to Section 3.2.1, page 22.
  • Page 11 SMA Solar Technology AG 1  Introduction Figure 1.3 Overview of the installation area PELV (safe to touch) Device grounding Ethernet interface x 2 RS485 interface (not in use) Live Parts AC terminals PV terminals Miscellaneous AC overvoltage protection (SPDs) DC overvoltage protection (SPDs) PV load-break switch Table 1.2 Overview of the installation area...
  • Page 12: Installation

    2  Installation SMA Solar Technology AG 2 Installation 2.1 Environment and Clearances Figure 2.6 Mount upright on vertical surface. A backward tilt of ten degrees is allowed. Figure 2.1 Avoid constant contact with water Figure 2.7 Avoid dust and ammonia gases INFORMATION Figure 2.2 Avoid direct solar irradiation...
  • Page 13: Mounting The Wall Mounting Bracket

    SMA Solar Technology AG 2  Installation 2.2 Mounting the Wall Mounting Bracket Figure 2.8 Safety clearances in mm INFORMATION The safety clearances to other objects must be maintained to ensure sufficient air circulation (see figure 2.8). Figure 2.9 Dimensions of wall mounting bracket in mm...
  • Page 14: Mounting The Inverter

    2  Installation SMA Solar Technology AG 2.3 Mounting the Inverter INFORMATION Use of the wall mounting bracket delivered with the inverter is mandatory. Warranty claims will expire if the inverter is operated without the wall mounting When handling the inverter observe the local health and bracket.
  • Page 15: Disassembling The Inverter

    SMA Solar Technology AG 2  Installation Observe ESD safety regulations. Discharge any electrostatic charge by touching the grounded enclosure, before handling any electronic component. Procedure: 1. To open the cover, loosen the three lower front screws using a TX 30 screwdriver. The screws are captive screws and cannot fall out.
  • Page 16 2  Installation SMA Solar Technology AG IMI Detection INFORMATION The inverter has a built-in IMI/RCMU (Insulation Monitoring Cables with multi-strand, fine-strand or extra Interrupter / Residual Current Monitoring Unit). The inverter fine-strand conductors can be used for AC acts on residual DC current and a sudden change in the connection (see figure 2.15 and 2.16).
  • Page 17: Cable Entry

    SMA Solar Technology AG 2  Installation LEAKAGE CURRENT HAZARD Insufficient grounding of the inverter can lead to serious injuries or lethal injuries. • Ensure the correct grounding of the devices by a certified electrical installer. 2.7 Cable Entry The mounting brackets for the cable glands are already pre-mounted.
  • Page 18: Pv Connection

    2  Installation SMA Solar Technology AG 2.9 PV Connection 2.9.1 External PV Array Junction Do NOT connect PV to ground! Boxes PV strings must be connected to the DC input via an external PV array junction box. The PV array junction box connects the PV strings of the PV array and protects the individual strings against overcurrent with appropriate fuse protection.
  • Page 19 SMA Solar Technology AG 2  Installation Figure 2.23 Cables with different conductors (from top to bottom): multi-strand, fine-strand and extra fine-strand 1. Switch the PV load-break switch on the inverter to "Off" and, if available, also on the PV array junction box.
  • Page 20: Closure

    3  Initial Setup and Start SMA Solar Technology AG • Local commissioning and service tool (LCS-Tool). The LCS tool can be used for configuring one or more inverters. 3.1.1 Operating modes The inverter has five operation modes, indicated by LEDs.
  • Page 21: Display

    SMA Solar Technology AG 3  Initial Setup and Start On grid (green LED glowing) The inverter is connected to the AC grid and feeds into the grid. The inverter disconnects from the utility grid in the following cases: • The inverter recognizes abnormal grid conditions (depending on the grid code).
  • Page 22: Initial Setup Via Lcs-Tool

    Customer-specific country and thus will void the warranty. data sets can be provided by SMA and imported via the LCS tool (see installation manual of the SMA Inverter • Make sure that the cables are correctly connected to Manager / SMA Digital I/O Box / LCS Tool).
  • Page 23: Configuring The Fallback

    SMA Inverter Manager and a superior control unit (e.g. SCADA system or Power Plant Controller) see installation manual of the SMA Inverter Manager / SMA Digital I/O Box / LCS Tool. INFORMATION Observe the specifications of your electric utility company.
  • Page 24: Service

    4  Service SMA Solar Technology AG 4 Service 4.1 Troubleshooting and Repair The information is organized in tables showing messages appearing in the LCS tool, known as events. The tables contain descriptions of events as well as explanations of which actions to take when an event occurs.
  • Page 25 SMA Solar Technology AG 4  Service Status Description Measure DNO SMA message Service Line 34–37 The residual-current monitoring Turn off both DC and AC supply unit (RCMU) detected an and wait until the display turns off. overcurrent. Then turn on DC and AC supply and observe if the event reoccurs.
  • Page 26 4  Service SMA Solar Technology AG PV-related events Status Description Measure message Service Line PV current is Too many PV modules Check number of strings in parallel too high/ connected in parallel. Should and current ratings. Has the current waiting...
  • Page 27 SMA Solar Technology AG 4  Service Status Description Measure message Service Line 2052, Transmission of the Grid Code 2053 from the SMA Inverter Manager to the inverter has started/ended. 2054 Transmission of the Grid Code If this event occurs frequently, from the SMA Inverter contact Service.
  • Page 28 4  Service SMA Solar Technology AG Status Description Measure message Service Line 219– Internal error. Voltage Contact the Service. measured before and after the relay differs too much. 225– Failure in memory/EEPROM. Restart the inverter. If the event 240, persists, call Service.
  • Page 29: Maintenance

    SMA Solar Technology AG 4  Service Events Caused by the Self-Test Description Measure Service Line PV input current is negative. Sensor fault. Check the polarity of the PV system. If polarity is correct, call Service. 264, Measurement circuit test failed.
  • Page 30: Technical Data

    5  Technical Data SMA Solar Technology AG 5 Technical Data 5.1 Specifications Parameter STP 60-JP-10 Nominal apparent power 60000 VA Nominal active power 60000 W Reactive power range 0 to 60000 var Nominal AC voltage 3 / PE; 420 V (50 Hz) 3 / PE;...
  • Page 31 SMA Solar Technology AG 5  Technical Data Parameter STP 60-JP-10 Enclosure Dimensions (W / H / D) 740 × 570 × 306 mm Weight 75 kg Acoustic noise level 58 dB(A) (typical) Table 5.1 Specifications at nominal grid voltage at nominal grid voltage, Cos(phi) = 1.
  • Page 32: Compliance

    5  Technical Data SMA Solar Technology AG 5.2 Compliance International standards STP 60-JP-10 Efficiency Peak efficiency, standard: EN 50530 JIS efficiency, Standard: JIS C 8961 EC low-voltage directive 2014/35/EU EC directive for electromagnetic compatibility (EMV) 2014/30/EU Safety IEC 62109-1/IEC 62109-2...
  • Page 33: Installation Conditions

    Prevent dust and ammonia gases. * Potential power reduction above 45°C (for further information see technical information "Efficiencies and Derating") ** Installation at altitudes > 2000 m are possible on request; contact SMA Solar Technology AG for this. Table 5.6 Installation conditions...
  • Page 34: Torque Specifications

    5  Technical Data SMA Solar Technology AG 5.4 Torque Specifications 5.5 Specifications for Grid Protection Parameter Specification Maximum inverter current, I 87 A ACmax Recommended type of time-lag fuse gL/gG 100 to125 A (IEC 60269-1) Recommended circuit breaker type B or C...
  • Page 35: Technical Data Of The Communication Interface

    SMA Solar Technology AG 5  Technical Data 5.6 Technical Data of the Communication Interface Interface Parameter Parameter details Specification Ethernet Cable Cable sheath diameter ( ⌀ ) 2 x 5 to 7 mm Cable type STP cable (Shielded Twisted Pair,...
  • Page 36: Ethernet Connections

    5  Technical Data SMA Solar Technology AG 5.7 Ethernet Connections Table 5.4 Pin assignment of the RJ45 plug for Ethernet Color standard assignment Cat. 5 Cat. 5 Ethernet T-568A T-568B Figure 5.5 Network topology 1. RX+ Green/white Orange/white Linear daisy chain 2.
  • Page 37: Contact

    SMA Solar Technology AG 6  Contact 6 Contact If you have technical problems with our products, please contact the SMA Service Line. We require the following information in order to provide you with the necessary assistance: • Inverter device type •...
  • Page 38 SMA Solar Technology www.SMA-Solar.com...