Data Transmission; Reading And Writing Of Data - SMA SUNNY TRIPOWER 60 Technical Information

Sunspec modbus interface
Hide thumbs Also See for SUNNY TRIPOWER 60:
Table of Contents

Advertisement

Product Description
3.4.4

Data transmission

In accordance with the Modbus specification, only a specific volume of data can be transported in
a single data transmission in a simple protocol data unit (PDU). The data also contains function-
dependent parameters such as the function code, start address or number of Modbus registers to
be transmitted. The amount of data depends on the Modbus command used and has to be taken
into account during data transmission. You can find the number of possible Modbus registers per
command in Section 3.5.
With data storage in the Motorola format "Big Endian", data transmission begins with the high byte
and then the low byte of the Modbus register.
3.5

Reading and Writing of Data

The Modbus interface can be used via the protocol Modbus TCP. Using Modbus TCP enables
read- and write access (RW) to the Modbus register.
The following Modbus commands are supported by the implemented Modbus interface:
Modbus command
Read Holding Registers
Read Input Registers
Write Single Register
Write Multiple Registers
Read Write Multiple Registers
1
Number of Modbus registers transferable as data block per command
12
STP60-SunSpec_Modbus-TI-en-12
Hexadecimal value
0x03
0x04
0x06
0x10
0x17
SMA Solar Technology AG
Data volume
(number of registers)
1 to 125
1 to 125
1
1 to 123
Read: 1 to 125, Write: 1 to 121
1
Technical Information