Table Ic 120 (Inverter Controls Nameplate Ratings) - SMA SUNNY TRIPOWER 60 Technical Information

Sunspec modbus interface
Hide thumbs Also See for SUNNY TRIPOWER 60:
Table of Contents

Advertisement

SMA Solar Technology AG
5.2.5

Table IC 120 (Inverter Controls Nameplate Ratings)

Description / Number code
Header:
Model ID (ID):
40238
120 = SunSpec Nameplate Model
Number of the following Modbus registers in accordance with
40239
the PICS table (L): 26
Fixed block:
DER type (DERTyp):
40240
4 = PV device
Continuous active power capability (WRtg), in W
40241
(40242), (SMA: SGridNom*P_LIM_IF_Q).
40242 Scale factor continuous active power capability (WRtg_SF): 3
Continuous apparent power capability (VARtg) in VA
40243
(40244), (SMA: SGridNom).
Scale factor continuous apparent power capability (VARtg_SF):
40244
3
Continuous reactive power capability in quadrant 1
40245
(VArRtgQ1), in var
Continuous reactive power capability in quadrant 2
40246
(VArRtgQ2), in var
Continuous reactive power capability in quadrant 3
40247
(VArRtgQ3), in var
Continuous reactive power capability in quadrant 4
40248
(VArRtgQ4), in var
Scale factor continuous reactive power capability (VArRtg_SF):
40249
3
Technical Information
VArRtg_SF
(40249), (SMA: SGridNom).
VArRtg_SF
(40249).
VArRtg_SF
(40249).
VArRtg_SF
(40249), (SMA: SGridNom).
STP60 SunSpec Modbus Profile – Assignment Tables
1
1
1
WRtg_SF
1
1
VARtg_SF
1
1
1
1
1
1
1
STP60-SunSpec_Modbus-TI-en-12
uint16
RO
uint16
RO
enum16
RO
uint16
RO
sunssf
RO
uint16
RO
sunssf
RO
int16
RO
int16
RO
int16
RO
int16
RO
sunssf
RO
23