LEDs
LED
Color Meaning
RUN
green This LED indicates the terminal's operating state:
off
flashing uniformly
flashing slowly
on
flashing rapidly
STATUS1,
green The respective channel is carrying out a measurement; the test specimen is live.
STATUS2
ERROR1,
red
Wire breakage. The resistance is outside the valid range.
ERROR2
4.6.2

Electrical connection

Recommended cables
In order to ensure trouble-free and low-noise measurement we recommend using shielded cables. The cable
screen should be connected thoroughly with the DIN rail near the terminal.
2/4-wire connection
Fig. 29: Connection
Both channels of the EL3692 are in 4-wire mode as standard.
Measurements on live objects
Measurement of live test specimens (DuT) is only permitted if no current flows through the test specimen.
EL3692
State of the EtherCAT State Machine: INIT = initialization of the
terminal
State of the EtherCAT State Machine: PREOP = function for
mailbox communication and different standard-settings set
State of the EtherCAT State Machine: SAFEOP = verification of the
sync manager channels and the distributed clocks.
Outputs remain in safe state
State of the EtherCAT State Machine: OP = normal operating state;
mailbox and process data communication is possible
State of the EtherCAT State Machine: BOOTSTRAP = function for
terminal firmware updates
Version: 2.1
Installation