Flowserve PMV D3 User Instructions page 28

Digital positioner
Table of Contents

Advertisement

The Setup Menu is used for various settings.
Actuator
Type of actuator
Rotating actuator.
Rotating
Linear
Linear actuator.
Lever
Only for linear actuator.
Lever stroke
Stroke length to achieve correct display.
Calibration of positions to achieve correct display.
Level cal
Direction
Direct
Direct function (signal increase opens). Indicator/spindle rotates
counter-clockwise.
Reverse
Reverse function.
Character
Curves that show position as a function of input signal.
Linear
Equal %
See diagram.
Quick open
Sqr root
Custom
Create own curve.
Cust chr
Specify number of points
# of point
(3, 5, 9, 17, or 33)
Enter values on X and Y axes.
Cust curve
Curr range
0%=4.0 mA
100%=20.0 mA Possibility of selecting which input signal values will correspond to
0% and 100% movement respectively. Examples of settings:
4 mA = 0%, 12 mA = 100%, 12 mA = 0%, 20 mA = 100%.
PMV D3 Digital Positioner
FULL MENU
SETUP
Size of actuator
Small
Medium
Large
Texas
28
FCD PMENIM0001-06 A5 09/16
Time out
10 s
25 s
60 s
180 s
y
Qo
Sqr
Lin
Eq%
Signal
x

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents