Digital positioner
Table of Contents

Advertisement

Temp
On/Off
Low temp
High temp
Hysteresis
Alarm out
Valve act
Valve act
No action
Goto open
Goto close
Manual
PMV D3 Digital Positioner
Alarm based on temperature
Temperature alarm on/off.
Temperature setting.
Temperature setting.
Allowed hysteresis.
Select ON/OFF offers output on terminals.
Behavior of valve when alarm is generated.
Alarm generated only. Operations not affected.
C+ gives full pressure and valve moves to fully
open position. Positioner changes to position
Manual.
C- gives full pressure and valve moves to fully
closed position. Positioner changes to position
Manual.
Valve stays in unchanged position. Positioner
moves to position Manual.