Do you have a question about the Limitorque QX and is the answer not in the manual?
Questions and answers
David Cozart
May 13, 2025
I have a QX5 that is showing motor fault and will not clear. We even tried to power cycle the unit to see if it would. Anything we can check would be helpful
1 comments:
Mr. Anderson
May 21, 2025
For a Flowserve QX5 motor fault that will not clear, the following troubleshooting steps can be taken:
1. Check the Fault Message: Determine the specific fault message, such as “LOW LINE VOLTAGE” or “MOTOR FAULT”.
2. Low Line Voltage: If the fault is “LOW LINE VOLTAGE”, verify that the line voltage supplied to the actuator is within the required range. Restore power to safe levels if it is too low.
3. RAM Error: If the display shows “RAM ERROR”, the QX processor will automatically reset to clear the corrupted memory. After the reset, reissue any uncompleted commands.
4. ROM Error: If the display shows “ROM ERROR”, the actuator operation is disabled. Set the selector switch to “STOP” and reinitialize the unit, following the on-screen prompts.
5. Motor Inspection: If the motor assembly is suspected to be faulty: - Turn off all power sources (main and control power). - Disconnect and remove the motor assembly carefully. - Inspect motor components such as the rotor, coupling, and connectors for damage or misalignment. - Reinstall the motor, route wiring properly, and reconnect the motor wiring only after mounting.
6. Thermostat Check: If related to overheating, check and change the motor thermostat if necessary.
7. Reinitialization: If faults persist, reinitialize the actuator by following the initialize routine shown on the display.
These steps address electrical, memory, and mechanical issues related to persistent motor faults.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Contents Important Notes Quick Start 2.1 Calibrate – Position Limits 2.1.1 Electrical Operation Feature 2.1.2 Handwheel Operation Feature 2.1.3 Entering the Setup Mode 2.2 DDC Option 2.3 Check the Settings Installation and Operation 3.1 Preparing the Stem Nut...
Page 3
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.9 Modutronic Option 4.9.1 Status 4.9.2 Proportional Band 4.9.3 Fail Position 4.9.4 Deadband 4.9.5 Polarity (20 mA) 4.9.6 Delay After Stop 4.9.7 4-20 mA Signal Range 4.9.8 Set High Reference 4.9.9 Set Low Reference 4.9.10 Modutronic LCD Display...
Page 4
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.16 Change Analog Out 4.16.1 APT Polarity Option 4.16.2 ATT Polarity Option 4.17 Remote Mode 4.18 Local Control 4.18.1 LED Customization 4.19 ESD (Emergency Shutdown) Overrides 4.19.1 ESD Override 4.19.2 Inhibit 4.19.3 Local Command 4.19.4 Stop...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 1.1 – QX-05 Actuator OPTIONAL Piece Description Piece Description Piece Description Handwheel Control Knob Motor Declutch Lever (QX-05) Ground Lug Certification Nameplate Oil Fill Baseplate Tag Nameplate Controls Cover Conduit Entry...
Page 8
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 NOTE: Removal of any cover, other than the terminal compartment cover, will invalidate the unit warranty. Exposure of actuator components to an environment that results in deterioration of internal components will also invalidate the unit’s warranty.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Quick Start Quick Start provides step-by-step instructions for commissioning each QX actuator. These instructions are for the following: • Position limits calibration – can be performed one of two ways: 1. Electrical operation: See Section 2.1.2, Electrical Operation Feature.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 2.1 Calibrate Position Limits 1. Confirm that the QX actuator is correctly installed on the valve as described in Section 3 Installation and Operation. 2. Refer to the nameplate for the correct main power supply voltage. Switch on the main power to the unit.
Page 11
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 CAUTION: Do not adjust close stop while stop is loaded. It is highly recommended that the stops be turned until they are almost removed from the housing before setting the limits. Once the limits have been set, then the stops maybe tightened.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 2.1 – Electrical operation Switch to STOP STOP CLOSE VALVE SAVE CLOSE SET CLOSE CLOSE VALVE CLOSE VALVE OK ? RETURN TO STOP OK ? LIMIT OK? POSITION LIMIT? LOCAL “NO ” operates...
Page 13
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Closed Position Limit 1. “SET CLOSE POSITION LIMIT?” is displayed on the LCD. 2. Select “YES.” The “CLOSE VALVE - OK?” is displayed. 3. Depress the declutch lever, and at the same time slowly rotate the handwheel until the clutch is fully engaged.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 2.2 – Handwheel operation STO P YE S YE S YE S SET CLOS E CLOSE VALVE SAVE CLOS E POSITION LIMIT? OK ? LIMIT OK? Declutch actuator; Rotate handwheel to “...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 2.1.3 Entering the Setup Mode To access the Setup Mode after initial setup has been exited, use these steps: 1. Place the red selector knob in the “STOP” position. 2. Within 10 seconds, place the black control knob in the “YES” position, then the “NO” position, then again in the “YES”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Installation and Operation 3.1 Preparing the Stem Nut The QX has two (2) basic base designs: • Torque-only (90º) operation • Multi-turn operation (up to 20 multi-turn rotations - 7200º total) 3.1.1 Torque Applications Standard B4/B4E Base The standard QX actuator base is the stem nut for torque-only.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Disassembly – Flange 2 1. Remove the two torque nut mounting screws and remove the torque nut. 2. Machine the torque nut to suit the valve stem or gearbox input shaft. Ensure sufficient clearance for a smooth, sliding fit.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3.2 Mechanical Installation onto Valve or Gearbox Before installing the actuator onto a valve or gearbox, check the following to ease installation: • Verify that mounting flange is suited dimensionally to mate with the actuator base. Ensure that it is perpendicular to the valve stem.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3.3.3 Sealing Cable/Conduit Entries The sealing of cables and conduit entries should be done in accordance with National Standards or the Regulatory Authorities that have certified the actuators. This is particularly true for units that are certified for use in hazardous areas where the method of sealing must be to an approved standard and cable glands, reducers, plugs, and adapters must be approved and separately certified.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Table 3.2 lists the maximum allowable voltage and current parameters for the terminal block control terminals. Table 3.2 – Terminal block rating; power terminals Description 30 AMP 20 AMP 15 AMP STD Rating...
Note 1: Refer to unit nameplate. 3.3.7 Network Installations The Limitorque QX offers a number of network options: DDC-Modbus, Foundation Fieldbus H1, Profibus DP_V1, Profibus PA, and DeviceNet. Ensure that the network cable type is Belden 3074F, Belden 3105, Belden 9841 or another cable that is within 5% of the following specifications.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 3.7 – Standard wiring diagram - three phase shown NOTE: Most current wiring diagram is shipped within the terminal compartment of the QX. View of terminal block Three-phase supply Close Reversing...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 CAUTION: Do not melt the insulation. 6. Connect the network cables to the QX actuator terminal block per Table 3.3 and appropriate wiring diagram. Table 3.5 details a connection for the loop topology.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Table 3.5– Loop topology connections Terminal Block Number DATA-A1* (-) DATA-A1 (+) DATA-A2* (-) DATA-A2 (+) Surge Protection In terms of voltage, DATA is negative with respect to DATA*. NOTE: Surge protection must be grounded to be effective.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Cable Preparation Prepare the network cable for connection to the QX actuator terminal block as follows in Figure 3.8 through 3.11. Table 3.6 details connections for Foundation Fieldbus. Table 3.6 – Foundation Fieldbus connections...
8 amps (4 amps for NEC Class 2) may be passed along the hi-way from a suitable power source. Two conductors are used for the CAN bus signals, CAN_H and CAN_L, which are usually smaller in diameter. Flowserve recommends Belden 3082A cable for connecting to a DeviceNet network.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 3.12 – Terminal Block Shield SHIELD-TERMINAL BLOCK M3 X 5 SELF LOCK SCREW USE QTY. OF TWO (2) M3 X 5 SELF LOCK SCREWS TO MOUNT SHIELD. USE 2 SCREWS FROM TERMINAL BLOCK OR FROM END USERS BAG.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3.5.2 View the Existing Settings All the existing setup data may be viewed on the LCD display by following a simple step-by-step dialog that may be selected in the following languages: English (default), Spanish, French, German, Italian, Portuguese, Russian, Malay, Mandarin, Katakana, and Turkish.
Page 32
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 If the calibration requires adjustment: 1. Select “NO” at the “SET OPEN POSITION LIMIT?” prompt. 2. Repeat the “SET CLOSE POSITION LIMIT?” routine. NOTE: The green LED is the default setting for indicating the (CLOSE) position.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 1. Move the red knob to “LOCAL” and move the black knob in the intended direction. LCD display will read: CLOSE VALVE OPEN VALVE RETURN TO STO P RETURN TO STO P 2.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3.6 Operating the QX Actuator 3.6.1 Manual Operation Operate the actuator with the handwheel as follows: Depress the declutch lever and, at the same time, slowly rotate the handwheel until the clutch is fully engaged.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3.6.4 Remote Control Once the position limits have been set, and “REMOTE” mode is enabled: 1. Place the red selector knob in “REMOTE” to permit command control by a remote device. Local “OPEN/CLOSE”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Table 3.10 – LED Indicators – default settings LED Indicator Operation Description Yellow Green Valve is fully open (Red knob in “REMOTE”) Valve is fully close (Red knob in “REMOTE”) Blinking Valve is closing (Red knob in “REMOTE”) Blinking Valve is opening (Red knob in “REMOTE”)
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Customizing the Actuator The actuator settings can be customized; i.e., the default settings can be changed and the purchased options can be configured. Language selection can also be customized. At the “SETUP IN ENGLISH?” prompt, select “NO” to move between the following languages: English, Spanish, German, French, Italian, Portuguese, Russian, Malay, Mandarin, Katakana, and Turkish.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 7. When configuration is complete, answer “YES” to “EXIT SETUP?” Alternatively, the “SETUP” mode may be terminated at any time by moving the red selector knob from “STOP” to “LOCAL” or “REMOTE.” All the changes made so far will automatically be saved.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.4 Valve Setup Valve setup enables the actuator to be changed to suit the type of valve that it is mounted on. 4.4.1 Close Direction Default = CW to Close The majority of valves require clockwise (CW) rotation of the actuator drive sleeve when viewed from above the actuator.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.5 Torque Switch Timer Torque switch timer permits a user to select a time for the torque switch to time out once the actuator determines that it has reached its torque seat. The torque switch timer can be adjusted from zero (0) seconds to a maximum of ten (10) seconds. The default is five (5) seconds.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.6 Operating Time All QX units are shipped with default operating time values based on unit size. The different sized units each have a specific range of operating times: • QX-1: 5-20 sec, default 15 sec •...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.7.1 Close Torque Valve or Open Torque Valve The output torque from the actuator to close or open the valve may be configured between 40% and 100% of the rated torque as stated on the actuator nameplate (See Figure 4.10), in 1% increments (unless limited by the factory).
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4. Inspect for correct operation. If the position limits are set adjacent to each other, then an error message will be displayed: “KEEP OPEN (CLOSE) LIMIT.” The position calibration is now complete. The actuator will function as ordered.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.11 – Electrical operation Switch to STO P STO P CLOSE VALVE CLOSE VALVE CLOSE VALV E SAVE CLOSE SET CLOSE RETURN T O STO P POSITION LIMIT? OK ? OK ?
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.9 Modutronic Option The Modutronic option enables the actuator to be controlled via a milliamp input signal. • If the Modutronic option has been purchased, it is automatically calibrated when position limits are set. No further adjustments are required, unless the defaults do not suit the application.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.9.6 Delay After Stop Default setting = 0 seconds To change from the default setting, select “NO” to adjust the length of delay time after the actuator stops modulating. The delay after stop is adjustable from 0-60 seconds.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.14 – Modutronic signals A PPLY HIGH LEVEL HIGH REFERENCE SET HIGH “ SET LOW C ONTROL SIGNA L (OK)-EXIT REFERENCE-OK? REFERENCE ” “ CHANGE SET LO W APPLY L OW LEVEL LOW REFERENCE MODUTRONIC”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.10.2 Network Address Default = 1 Network address allows user to assign a unique network address to an actuator. 1. The network address must be entered in accordance with the Instrument Data Sheet, and care must be taken to ensure that the same address is not used anywhere else in the same network.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.10.6 Proportional Band Proportional band is the range of errors between position and demand signal that will produce reduced speed (pulsing). Default = 15% To change from the default, select “NO” until the required value is displayed. The value is adjustable between 1% and 100%, in 1% increments.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.11.1 Status Default = ON FF Status enables user to change from the default condition to turn on and off the digital control capability of the actuator. 4.11.2 Terminate Bus Should a user select to make this unique actuator the termination point for the network, select “YES.” If not, then “NO.”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 13. For no COMM LOSS ACTION, select YES. For setting COMM LOSS ACTION, select NO. If POSITION is chosen, as action, COMM LOSS MOVE TO (XXX%)-OK? is displayed. Select NO to set desired position.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 QX Multi-control Mode Operation - The QX is equipped with the ability to hardwire to digital inputs, set-up for analog control (Modutronic), or control via network protocols. In order to utilize this feature, select “Multi-control mode”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 To Change from the Default Range: Select “NO” to adjust the value between 1% and 50%, in 1% increments to suit the application. Figure 4.19 – DN Option CHANGE STATUS BAUD RATE...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Select “NO” until the display indicates the required value of percentage OPEN at which the pulsing should start. Adjustable in 1% increments as listed: Closing = 0% to 99%. Opening = 1% to 100%.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.22 – Change Analog Out CHANGE ANALOG STATUS STATUS FUNCTION ANALOG OUT ? OUT 1? ON-OK? APT-OK? OUT 2? ON-OK? ATT-OK? Figure 4.23 – Change Analog Out Voltage – APT CALIBRATE...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.25 – Change Analog Out Voltage – ATT CALIBRATE 10VDC HIGH SIGNAL? If 5VDC option selected: “5VDC” will be displayed. SAVE If 5VDC option selected: SETTINGS? “POLARITY 5VDC” will be displayed.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 3. Select “NO” to select 4 ma/0 VDC2. Select “YES” to enter the “POLARITY” display. 4. Select “NO” to choose between: 20 mA = OPEN 20 mA = CLOSE 5. Select “NO” to recalibrate new value (low end 3.4-4.5 mA; high end 19.5-21 mA) as shown on meter. New value will not be shown on display.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.18 Local Control “LOCAL CONTROL” mode changes how the local control switches and display are used from the default settings. Default = On & Maintain Mode NOTE: User may select to disable the LOCAL CONTROL, which prohibits the cycling of the QX from OPEN to CLOSE or REVERSE.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.19.1 ESD Override It may be desirable that ESD override other events. These events are selectable. The “>” symbol after ESD indicates that ESD will override that particular event. Sections 4.19.2 through 4.19.12 list the choices.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 • Three-wire Maintain Control (default except Modutronic) Requires two maintained contacts for self-maintained control in OPEN or CLOSE direction. • Three-wire Inching Control Requires two momentary contacts to OPEN or CLOSE the valve, or STOP it in mid-travel.
Page 69
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 • Set as enabled, partial stroke enable function, signal present = active Input 2 (normal default – Close Inhibit) terminal 35: • Set as enabled, partial stroke enable function, signal absent = active The partial stroke enable signals are setup as redundant signals for safety.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.20.4 Custom Input Mode #2 – Momentary ESD/CSE (Optional) Custom software is available for the QX that permits the user to establish certain performance characteristics momentary contact closure ESD and 4-wire remote control.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 removed, then the timer is canceled and will start fresh with the next assertion. You cannot change that Input 0 is ESD, but it can be enabled/disabled, set to signal present/absent, or you can change the ESD action.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.32 – Monitor relay CHANGE SELECT L0CAL LOCAL STOP OVERTORQUE INHIBIT SIGNAL ESD SIGNAL MONITOR RELAY? SETTINGS? ENABLED-OK? ENABLED-OK? DISABLED-OK? DISABLED-OK DISABLED-OK? DISABLED-OK? DISABLED-OK? ENABLED-OK? ENABLED-OK? ENABLED-OK? The three following options will only show if the customer has purchased and enaled custom option 1.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 process conditions, and after a plant shutdown or actuator/valve overhaul. The user may select to reset the torque profile at any time. 1. Select “RESET TORQUE PROFILE?” from the “RESET DIAGNOSTICS” routine.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 4.24 LCD Contrast Permits adjustment of the viewing contrast of the LCD. 1. Select “YES” to enter the “LCD CONTRAST” display. 2. Select “NO” to adjust contrast to desired level. Figure 4.35 – LCD contrast...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 4.37 – Change valve data CHANGE VALVE CHANGE VALVE CHANGE VALVE VALVE TYPE CHANGE VALVE NOTE 1: DATA? S/N? MODEL #? TYPE? UNDEFINED -OK? Valve type "UNDEFINED" is only shown until the valve type is chosen.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Troubleshooting WARNING: This actuator is non-intrusive. Do not open the control compartment on the actuator unless absolutely necessary. It was sealed in dry, clean conditions in the factory and entry to this compartment should not be necessary.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 5.1 View Diagnostics Routine 1. Enter “VIEW DIAGNOSTICS” as detailed in Section 5.3, View Diagnostics. 2. Review the various displays to try to find the reason the actuator will not operate. The displays that may help to isolate the fault are as follows: •...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Actuator Fails to Operate from REMOTE Controls 1. Check that the actuator will operate from “LOCAL.” If not, then carry out the checks described below. 2. Check that the red knob is in “REMOTE.”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 5.2.5 Status Messages Normal display status is listed in Section 3.6.5, Local Indication. Status or alarm messages are listed below. Once a status or alarm condition occurs, the message will be displayed on the bottom line of the Local Control Station (LCS) screen until the condition is addressed and cleared.
Page 82
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 ---% OPEN, TORQUE TIMEOUT – The torque switch timed out after the actuator determined that it has reached its torque seat “SET LIMITS” – Normal display if red selector knob is in “LOCAL” or “REMOTE” and position limits have not been set “INITIALIZE”...
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 “RAM ERROR” After the reset, the display will read normally. Any momentary commands (DDC command, momentary pushbutton, etc.) that were not completely executed must be reissued. ROM Error The QX processor continually checks EPROM for memory corruption errors. If corruption is detected, operation is disabled.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 5.5 View Motor Status Viewing “MOTOR STATUS” will provide information on the following: • If the three-phase power supply is connected correctly. • If autophase correction is in operation. • If there is a fault or loss of a phase.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Figure 5.6 – View identification VIEW TAG # SERIAL # ORDER # FIRMWARE REV. -OK? IDENTIFICATION? MOV257 -OK? M002567 -OK? 366765F E654 *Network revisions will only be displayed if the optional network board is installed within the QX.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 • “TURNS RECENT” – Number of drive sleeve revolutions since last diagnostic reset. See Section 4.22, Diagnostic Reset, for reset diagnostics instructions. • “CONTACTOR OPS” – Total number of contactor operations • “OPS RECENT” – Number of contactor operations since last diagnostic reset. See Section 4.22, Diagnostic Reset, for reset diagnostics instructions.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 5.10 View DNET Status? This selection permits the User to view pertinent information that summarizes the status of the DeviceNet option board Figure 5.9 – View DNET status NOT ONLINE - VIEW...
Page 89
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 • For a Group 2 Only device it means that the device is allocated to a Master. • For a UCMM capable device it means that the device has one or more established connections.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Maintenance Under normal operating conditions, the QX is a maintenance-free actuator. For ordinary applications, the actuator will require no formal maintenance program. However, if the actuator is used under severe service conditions or operated in a Hazardous Location, the following maintenance procedures are required: 1.
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Regulatory Information Application of Council Directive(s) 2004/108/EC; EMC Directive 2006/42/EC; Machinery Directive 2003/10/EC; Airborne Noise Directive 94/9/EC; ATEX Directive Standard(s) to which Conformity is Declared Machinery; EN 60204-1:2006+A1:2009 EMC - Emissions: EN 61000-6-3:2007+A1:2011...
Page 92
Limitorque QX Electronic Actuator FCD LMENIM3306-06 – 07/14 Applicable emissions standards EN61326-1 (CISPR11) Industrial Environments - Class A - Test Limits & Levels 30 MHz to 230 MHz 40 dB (μV/m) EN55011:2009+A1:2010 (CISPR11) 230 MHz to 1 GHz 47 dB (μV/m) 30 MHz to 88 MHz 90 dB (μV/m)
Page 93
Manufacturer’s Address 5114 Woodall Rd, Lynchburg, VA 24502 USA Importer’s Name Flowserve Flow Control(UK) Ltd., a Division of Flowserve (GB) Ltd. Import’s Address Euro House, Abex Road, Newbury, Berkshire, RG14 5EY England I, the undersigned, hereby declare that the equipment specified above conforms to the above Directive(s) and Standard(s) John Thilking Sr.
3. Consult the manufacturer if dimensional information on the flameproof joints is necessary. 7.2 Statement of Compliance with Applicable European Directives We, Flowserve Limitorque, 5114 Woodall Road, Lynchburg, VA, USA 24502, as the manufacturer of the equipment listed below: QX-1, 2, 3, 4, 5 electronic valve actuator. The QX is a non-intrusive electronic actuator. It is specifically designed for the purpose of being mounted to a quarter turn valve (or other apparatus) in order to move the valve from fully closed to fully open.
Page 96
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous applications under a Facsimile: 86-10-6561-2702 wide variety of industrial service conditions.
Need help?
Do you have a question about the Limitorque QX and is the answer not in the manual?
Questions and answers
I have a QX5 that is showing motor fault and will not clear. We even tried to power cycle the unit to see if it would. Anything we can check would be helpful
For a Flowserve QX5 motor fault that will not clear, the following troubleshooting steps can be taken:
1. Check the Fault Message: Determine the specific fault message, such as “LOW LINE VOLTAGE” or “MOTOR FAULT”.
2. Low Line Voltage: If the fault is “LOW LINE VOLTAGE”, verify that the line voltage supplied to the actuator is within the required range. Restore power to safe levels if it is too low.
3. RAM Error: If the display shows “RAM ERROR”, the QX processor will automatically reset to clear the corrupted memory. After the reset, reissue any uncompleted commands.
4. ROM Error: If the display shows “ROM ERROR”, the actuator operation is disabled. Set the selector switch to “STOP” and reinitialize the unit, following the on-screen prompts.
5. Motor Inspection: If the motor assembly is suspected to be faulty:
- Turn off all power sources (main and control power).
- Disconnect and remove the motor assembly carefully.
- Inspect motor components such as the rotor, coupling, and connectors for damage or misalignment.
- Reinstall the motor, route wiring properly, and reconnect the motor wiring only after mounting.
6. Thermostat Check: If related to overheating, check and change the motor thermostat if necessary.
7. Reinitialization: If faults persist, reinitialize the actuator by following the initialize routine shown on the display.
These steps address electrical, memory, and mechanical issues related to persistent motor faults.
This answer is automatically generated