Ra332; Figure 6: Rear View Of The Ra332 - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311
2.3

RA332

2.3.1
Key Features
2.3.2
Components
40
F
Front Panel Indicators: Mains lights up when the module is powered-up. Ready
indicator lights up after the module self-test is completed. The Link1 indicator lights
up when active.
Up to 16 analog inputs (voltage, current, DC transducers, probes);
Up to 32 digital inputs;
16-bit analog-to-digital converters, 256 points-per-cycle sampling rate;
Frequency response of DC to 3.0 kHz;
Fiber-optic interface to connect to the processing module;
Up to 2 km fiber-optic links;
Front panel mounting or internal panel mounting.
Figure 6
shows all the components of the RA332 module.

Figure 6: Rear view of the RA332

A
AC or DC power input.
B
Mains and Ready back panel indicators: Mains is lit when the module is powered-
up. Ready indicator lights up after the module self-test is completed.
C
Up to 16 analog inputs for voltage, current, or DC transducers, identified as 101 to
116.
Chapter 3 – Hardware Design