Sync Does Not Lights Up; Date Or Time Incorrect; Time Drift Throughout Operation Week; Rpv311 Firmware Update - GE RPV311 Technical Manual

Distributed multifunction fault recorder
Table of Contents

Advertisement

RPV311

SYNC does not lights up

2.3
2.4

Date or time incorrect

2.5

Time drift throughout operation week

3

RPV311 Firmware Update

RPV311-TM-EN-7
Opened link
Make sure that on IRIG-B signal is present at the optical or electrical input, and
connect signal if is not;
Verify the quality of the IRIG-B signal, in Web or Local Interface. If the signal is low
quality, try to use the optical input.
Make sure that time zone and daylight saving time have been properly configured
and set correctly if is not.
The equipment must be operating without an external reference.
Make sure that an IRIG-B signal is present at the optical or electrical input, and
connect signal if is not;
Verify the NTP/SNTP server and guarantee this alternative source of timing.
When installing the application software package accompanying the equipment
(refer to Software Installation), the Firmware Upgrade Tool (FUT) is installed and
associated having an files with extension .fw allowing an RPV firmware update to be
easily carried out by user.
The steps to be followed for updating the equipment firmware are:
1.
Request Alstom for the firmware file.
2.
Copy the file to the PC on which the RPV application software is installed
(see Software Installation). The file shall have a .fw extension.
3.
Double click file.
4.
A screen opens and if it is the first time connection between the local PC and
the equipment is made an acknowledgement message will appear in the
interface. Answer <
5.
Provide the RPV IP address in the 192.168.0.160 format and press <E
Chapter 16 – Maintenance and Troubleshooting
Check the links between RPV and
acquisition modules
> and press <E
>;
Y
NTER
>;
NTER
250